6

CONFIGURING THE FIELDSERVER AS A SECUTRON MODUL-R DRIVER SERVER

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” files provided with the FieldServer).

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Secutron Modul-R driver communications, the driver independent FieldServer buffers need to
be declared in the “Data Arrays” section, the FieldServer virtual node(s) need to be declared in the “Server Side
Nodes” section, and the data to be provided to the Client needs to be mapped in the “Server Side Map
Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

6.1

Server Side Connection Parameters

Section Title
Connections
Column
Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8

2

Baud*

Specify baud rate

150, 300, 1200, 2400, 4800, 9600 (Vendor
limitation)

Parity*

Specify parity

None (Vendor limitation)

Data_Bits*

Specify data bits

8 (Vendor limitation)

Stop_Bits*

Specify stop bits

1 (Vendor limitation)

Protocol

Specify protocol used

Secutron


Example

// Server Side Connections

Port , Protocol

, Baud , Parity

P1

, Secutron , 9600 , None

6.2

Server Side Node Parameters

Section Title
Nodes
Column Title Function

Legal Values

Node_Name

Provide name for Node

Up to 32 alphanumeric characters

Node_ID

Generic Node ID unique to port. Also used as panel number. 0-9

Protocol

Specify protocol used

Secutron

Port

Port to which node belongs

P1-P8

2

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.