Figure 1

ELECTRICAL BOX

WIRE NUTS

ELECTRICAL BOX COVER

Figure 2

IDENTIFY WHICH MODEL POWER VENTER YOU HAVE
CAUTION: Avoid applying excess pressure on the blower wheel when handling. This will cause an imbalance
of the blower wheel which will result in excessive vibration and premature motor failure.

REMOVAL

1. Remove motor cover. (See Figure 1)

2. Remove the electrical box cover and disconnect the conduit and wires. (See Figure 2) It is not necessary

to disconnect the wires from the Control Kit.

3. Remove the nuts securing the motor assembly, and pull the motor assembly straight off of the unit.

(See Figure 3)

4. Clean off any build-up inside the blower wheel housing.