Client side node descriptors – FieldServer Modbus Daniels FS-8700-15 User Manual

Page 6

Advertising
background image

FS-8700-15 Modbus Daniels Manual

Page 4 of 7


device is connected to the
FieldServer

FS-X20 Serves: Serial Port

Protocol

Specify protocol used

Modbus_Daniels

Baud*

Specify baud rate

110 – 115200, standard baud
rates only, 9600

Parity* Specify

parity

Even, Odd, None, Mark,
Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Handshaking*

Specify hardware
handshaking

RTS, RTS/CTS, None

Poll _Delay*

Time between internal polls

0-32000 seconds, 1 second


Example

// Client Side Connections

Connections
Port,

Protocol,

Baud, Parity,

Handshaking,

Poll_Delay

P1,

Modbus_Daniels,

9600,

Even,

None,

0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric
characters

Node_ID

Modbus station address of
physical server node

1-255

Protocol

Specify protocol used

Modbus_Daniels

Connection

Specify which port the device is
connected to the FieldServer

FS-X40 Serves: P1-P8, R1-R2
FS-X20 Serves: Serial Port


Example

// Client Side Nodes

Nodes

Node_Name,

Node_ID,

Protocol,

Connection

PLC 1,

1,

Modbus_Daniels,

P1