Furuno BC-6158 User Manual

Page 2

Advertising
background image

4.4 Battery charger(BC-6158)

4-14

V

I

28V

4.4.3 Battery charger (BC-6158)

Battery charger BC-6158 can charge clad type or pasteboard vent type batteries of up to

300 AH. It is a constant voltage/current charger which supplies a constant voltage of 28

V and a constant charging current of 20 A (30 A).

The power supply to the charger is connected to a tap of transformer T1 which is

selected according to the supply voltage.

The maximum charging current differs according to the capacity of the battery to be

charged. For example, for a battery of 200 AH the maximum charging current is 20 A

and for a 300 AH battery the current is 30 A. VR2 adjusts the maximum current to 20 A

or 30 A. VR1 adjusts the output voltage of the charger to 28 V. The thermal sensor is

mounted on the heat radiator of the charger, and it operates when the sensor detects a

temperature of 60 degrees.

20A(30A)

Fig. 4.4.4

Fig. 4.4.5 BC-6518 block diagram

110V

100V

0V

110V
100V

0V

K1

T1

U1/U2

Q1

Q4/Q5

CR3/Q3

Q2

VR1

VR2

30A

Breaker

CP1

FAN

S1

6o degrees

thermal sensor

FM1

CR2

TB 1

AC IN

TB 3

TB 2

(1, 2)

24V 5

CHARGE 6

0V 7

1 BATT+

2 BATT-

TB 3

1 BATT+

2 BATT-

3 BATT+

4 BATT-

R1,2,3,4

Full wave rectifier

Power conrol

Over current
detector

Voltage error
detctor

AMP.

05P0659 board

VR2
(Over current ADJ. VR:
Adjust to 20A)

VR1
(Over voltage ADJ. VR:

Adjust to 28V)

S1: 60 degrees
thermal sensor

Fig. 4.4.6 BC-6158 left side

Advertising