Falcon RACKMOUNT UPS PLUS FN4KRM-2TX User Manual

Page 7

Advertising
background image

Battery Packs

IMPORTANT: UPS can be used with only one Battery Cabinet.

FN rackmount battery modules utilize flame retardant batteries. They consist of (20) 12V, 7AH valve-regulat-
ed, sealed lead acid (VRLA) batteries in each module (Yuasa NP7-12). See replacement instructions on page
34.

To maintain the optimum battery life, the UPS should be installed in an environment with an ambient
temperature of 68ºF to 77ºF (20ºC to 25ºC). Due to the battery manufacturer specification, the FN Series UPS
batteries may be operated at 32ºF to 104ºF (0ºC - 40ºC) , but battery life will be substantially reduced if con-
tinuously operated at the higher temperature levels. Optional extended battery modules and external battery
charger modules are available through Falcon to extend the amount of battery runtime.

Internal Battery Charger

The internal battery charger located inside the UPS module utilizes energy from the utility power source to
continuously charge the UPS batteries. The charger operates in "constant power" mode. The UPS batteries
are being charged whenever the UPS is plugged in, turned on and operating from utility power. The internal
UPS battery charger output is rated at 1.9 amps.

Static Bypass Function

NOTE: Bypass power will only be available If the bypass input is connected at the time of UPS
installation.

A manual static bypass pushbutton is located on the FN front control panel. When the UPS is operating from
utility in the normal utility mode on-line state, depressing this button will cause the UPS to transfer to bypass.
Depressing the bypass button again will return the UPS to normal inverter operation.

Automatic Bypass Transfers

The FN Series UPS module will automatically switch to bypass mode under the following conditions: To
energize the connected load when the UPS is first turned on; encounters an overload; encounters an over
temperature condition; or upon a UPS failure condition. Should any of these events occur, the UPS will
automatically transfer to bypass mode, sound an audible alarm and provide a "bypass" indication on the UPS
module LCD display.

Output Filter

As with the input filter stage, the output filter maintains conducted (EMC) and RFI levels below FCC Class A
limits.

7

Advertising