GAS SPILLAGE SENSING KIT

Model: GSK-3, GSK-4, GSK-250M

Installation of a spillage SAFETY Switch is recommended for LP and Natural gas fired systems with draft
hoods, draft diverter, or gas barometric draft controls. This device is installed to detect flue gas spillage
caused by a blocked flue system and/or inadequate draft. This device MUST be installed by a qualified
installer in accordance with the manufacturer's installation instructions. Wiring MUST be in accordance
with the National Electrical Code and applicable local codes.

Before and after adding this safety control on existing appliances, an installation inspection in accordance
with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis
is recommended to determine the operating condition of the appliance.

CAUTION: Disconnect Electrical Power When Wiring Spillage Switch

LOAD RATING

MODEL

P/N

CONTACT

MATERIAL

AMPS

VOLTS

SETPOINT °F

RESET

SWITCH

TYPE

APPLICATION

GSK-3

46086400

GOLD

24VA

mV-24AC

180

MANUAL

SPST NC

Gas-fired mV or 24VAC

GSK-4

46086402

GOLD

24VA

mV-24AC

200

MANUAL

SPST NC

Gas-fired mV or 24VAC,

where slower response

time is a requirement

GSK-250M

46086404

SILVER

24VA

mV-24AC

250

MANUAL

SPST NC

Steam Boilers