Follett HCE1000A User Manual

Page 24

Advertising
background image

24

Refrigeration charge

All service on refrigeration systems must be performed in accordance with all federal, state and local laws. It is
the responsibility of the technician to ensure that these requirements are met. Recharging icemaker to other than
factory specifications will void the warranty.

R404A icemaker charge specifications

Model

Charge

Refrigerant

type

HCE1000A (air-cooled)

24oz (652g)

R404A

HCE1000W (water-cooled)

15oz (426g)

R404A

Refrigerant replacement requirements

Note: The evaporator and refrigerant tubing stubs are made of aluminum-bronze. When brazing copper tubing

to the stubs, it is important to have clean surfaces and use MG Slik-Sil 104 or equivalent brazing

stick for aluminum bronze brazing.

1. Non-contaminated refrigerant removed from any Follett refrigeration system can be recycled and returned

to the same system after completing repairs. Recycled refrigerant must be stored in a clean, approved
storage container. If additional refrigerant is required, virgin or reclaimed refrigerant that meets ARI
standard 700-88 must be used.

2. In the event of system contamination (for example, a compressor burn out, refrigerant leak, presence of

non-condensibles or moisture), the system must be repaired, evacuated and recharged using virgin or
reclaimed refrigerant that meets ARI standard 700-88.

3. Follett Corporation does not approve of recovered refrigerants. Improper refrigeration servicing procedures

will void the factory warranty.

Evacuation

Evacuate the system to a level of 500 microns. When the 500 micron level is reached, close all valves. Allow the
system to sit for approximately 20 minutes. During this period the system pressure should not rise. If the system
pressure rises and stabilizes there is moisture in the system and further evacuation is needed. If the pressure
continues to rise check the system for leaks.

Ambients Minimum

Maximum

Air temperature

1

50˚F/10˚C

100˚F/37.8˚C

Water temperature

2

45˚F/7˚C

90˚F/32.2˚C

1

Ambient air temperature is measured at the air-cooled condenser coil inlet.

2

Ambient water temperature is measured in the icemaker float reservoir.

Ice capacity test

Icemaker production capacity can only be determined by weighing ice produced in a specific time period.

1. Replace all panels on icemaker.
2. Run icemaker for at least 15 minutes.
3. Weigh and record weight of container used to catch ice.
4. Catch ice for 15 or 20 minutes.
5. Weigh harvested ice and record total weight.
6. Subtract weight of container from total weight.
7. Convert fractions of pounds to decimal equivalents (ex. 6 lbs 8oz = 6.5 lbs).

1440 min. x wt. of ice produced

=

Production capacity/24 hr. period

Total test time in minutes

8. Calculate production using following formula:
9. Calculated amount per 24 hours should be checked against rated capacity for same ambient and water

temperatures in Ice Production Tables.

Advertising
This manual is related to the following products: