FS-X20 Series FieldServer Start-up Guide (07-2005)

1. Pre-Installation Check List

1.1. Supplied equipment

The following components are supplied:

FS-X20 Series FieldServer, loaded with
Modbus RTU driver, SMT Ethernet
driver and any other drivers ordered.

1

FS-X20 Series Start-up Guide (T17005)

FieldServer

Configuration

Manual

(T17003)

FieldServer Utilities Manual (T17009)

Driver Manual(s) specific to all Drivers
ordered with the FieldServer.

Utility CD – note that the Utilities support
the following platforms only:

Windows XP

Windows 2000

Windows NT

Windows 98

Any additional Diskettes related to
special files configured for a specific
FieldServer.

Additional components as required -.
See Driver Manual Supplement for
details

An accessory bag consisting of the
following: :

DB9F/RJ45 Connection Adapter.
(Part Number FS-8917-02)

7-ft

Cat5

cable

with

RJ45

connectors at both ends (Part
Number FS-8915-10)

RS-232 Mini Tester, 25-pin (Part
Number FS-8915-13)

RS-485 connector (Part Number
FS-SPA59137)

Set of four different connectors
DB9M, DB9F, DB25M, DB25F (Part
Number FS-8915-11)

Power Supply

Connector for power (SPA59136)


1.2. Start-up

• Read this Start-up Guide in conjunction

with the Configuration Manual, the

1

Note that a default configuration file has

already been loaded onto the FieldServer.
Check the Driver Manual and the FieldServer
Configuration Manual for further information on
this file.

Driver Manual(s) and the Utilities
manual.


• The power socket mates with a

pluggable terminal block, connector, that
is supplied separately (SPA59136). The
terminal block is manufactured by
Phoenix Contact, model MSTB, (PN
1754465), No.30-12 AWG, 5-7 in/lbs
torque.


• USE COPPER CONDUCTORS ONLY
• Select an external power supply certified

for safety, for the correct destination
country and an output rating, which is
considered a NEC Class 2 circuit or is a
SELV Limited power source with the
following ratings:

• 9-30 VDC, 1A; OR 24 VAC, 50/60Hz,

0.5A

• INPUT VOLTAGE SPECIFICATION

• 24 VAC FLOATING

• Using a grounded VAC will cause

irreparable damage to the product.


• The operating environment for the

product is 0 to 60°C (32 to 140°F).