COMMUNICATIONS INTERFACES

RS-232 INTERFACE

16

Pin #

Function explanation

I/O

9

RS 232 Rx

INPUT

6

RS 232 Tx

OUTPUT

7

Ground

Location:

The RS-232 interface is standard on all SG series UPS models. The port is
located on the UPS rear panel, via a DB-9 female connector.

Supported Protocols

UPSILON 2000 & SEC Smart Mon

BAUD RATE ------- 2400bps
DATA LENGTH---- 8 bits
STOP BIT----------- 1 bit
PARITY-------------- None

DB-9 Connector Pin Assignment

When making a connection between a computer and the UPS RS-232 port,
always use the green cable supplied with the UPS.

There are communications options that WILL DISABLE the RS-232 port and
render it inoperable. The options are as follows:

a.

Internal SNMP/HTTP agent option installed into the UPS
communications option slot.

The following options WILL NOT affect the operation of the RS-232 port:

a.

Falcon Opto Coupler based signal interface board installed to the
communications option slot.

b.

Any Falcon relay based, dry contact signal interface board
installed into the communications option slot.

DB-9 Signals are not isolated and intended for connection to like RS-232
interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!


6
7
8
9

1
2
3
4
5

TX

RX

GEN

CAUTION

CAUTION

CAUTION

GND

Advertising