2kva & 3kva, Sg series, Ups plus – Falcon SG2K-2TXI User Manual

Page 26

Advertising
background image

SG Series

TM

UPS PLUS

®

2kVA & 3kVA

Electrical Input

Nominal AC Voltage

120V

230V

120V

230V

230V

AC Voltage Range

87 – 140V

170 – 275V

87 – 140V

170 – 275V

170 – 275V

Current – Amps

14.2

7.4

21.4

11.2

7.5

11.3

Frequency

50/60 Hz ± 5% (Auto – Tracking)

Power Factor Correction

> 0.95

Efficiency (Typical)

> 86%

> 85%

Electrical Output

Watts

1400

2100

1400

2100

AC Voltage
(Switchable)

100V
110V
115V
120V

200V
220V
230V
240V

100V
110V
115V
120V

200V
220V
230V
240V

120V

(700W

each

5-20R)

208V
220V
230V
240V

120V

(1400W

Max.)

208V
220V
230V
240V

Frequency

50/60 Hz (Auto Tracking )

Frequency Stability

± 0.3% (Battery Mode)

Voltage Regulation

± 2%

± 5%

± 3%

Step Load Change

± 7% for 100% load v ariation

Harmonic Distortion

< 3% Linear Load, < 5% Non -Linear Load

Overload

105% load for 50 Seconds

Crest Ratio

3:1

Battery

DC Voltage

72V

96V

Type

12V, 7AH Sealed Lead Acid Maintenance -Free

Back Up Time @ Full Load

@ 1/2 Load

7 Minutes

20 Minutes

5.5 Minutes

15 Minutes

7 Minutes

20 Minutes

5.5 Minutes

15 Minutes

Recharge Time

8 Hours to 90%

Battery times are approximate.

Transfer Time

Line Fails/Recovers

Zero

UPS to Bypass or Reverse

< 4ms

After Overload

Auto Transfer to UPS

Electrical Connections

Input

6’ Cord with

5-20P

6’ Cord with

6-20P, L6 -20P

or Schuko

6’ Cord with

L5-30P

6’ Cord with

6-20P, L6 -20P

or Schuko

6’ Cord with 6 -20P, L6 -20P

or Schuko

Output

(6) 5-15R or

(3) 5-15R &

(2) 5-20R

(6) IEC 320

or (1) L6-20R

(6) 5-15R or

(3) 5-15R &

(2) 5-20R

(6) IEC 320

or (1) L6-20R

(2) 5-20R & (1) L6 -20R

Contact the factory for other input/output options.

Environmental

Operating Temperature

0º C - 40º C (32º F to 104º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 Meter

<50dBA

Controls and Indicators

LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery

& Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp. , Over Load, Fault Alarm

Communications

RS-232 Serial Port (Bundled UPSilon 2000 Software)

Mechanical

Dimensions H x W x D inches (mm)

13.8 x 7.6 x 18.9 (350 x 193 x 480)

13.8 x 7.6 x 30 .0 (350 x 193 x 720)

Weight lb. (kg)

68.4 (31)

81.4 (37)

150.0 (68)

Agency Listing

-1T Models: UL 1778, CUL, FCC Class A
-2T Models: UL 1778, CUL , FCC Class A ; CE

available with Schuko plug only

UL 1778, CUL, FCC Class A

Available Options

Option A

60 Hz to 50 Hz Frequency Conversion

Option B

50 Hz to 60 Hz Frequency Conversion

Option C

SNMP/HTTP Network Card (Internal)

Option D

Standard Contact Closure Interface Card

Maintenance Bypass

Make-Before-Break External Wrap Around

External Battery Packs

Extended Run Time Battery Packs (minutes to hours)

Fast Battery Charger

Fast Charger internal to the Extended Battery Pack Cabinet (Required for battery times 2 hours or more.)

Model Number

SG2K-1T

SG2K-2T

SG3K-1T

SG3K-2T

SG2K-2TXI

SG3K-2TX

Nominal VA

2000

3000

2000

3000

24