Appendix C.6. “Illegal” Characters in Network Variable Names

Spaces

Spaces may not be used in Network Variable Names. The driver automatically replaces all spaces with
underscores at start-up.

Brackets Lonmaker truncates a name from where a bracket is used. e.g. a name like nviTest[1]Input shows as

nviTest . Brackets are therefore not able to be used in Network Variable Names.

Appendix C.7. Service types currently supported for network variable messages

Currently the service type for network variable update messages is fixed to acknowledged service. Request-
response service is used for network variable poll and network management fetch messages.

Appendix C.8. Combining Explicit and Implicit

To ensure undisturbed communication between the network management tool and the FieldServer during the
commissioning, binding or monitoring processes, the timeouts of the explicitly addressed variables (Map
Descriptors) might need to be set to values lower than the message timeouts used by the network management
tool (LonMaker for Windows).

LonWorks FieldServer Performance

No Desciption

Min Typ Max Units

1

FieldServer startup time with 4096 network variables

-

6.5

-

Minutes

2

Time to commission FieldServer with 4096 network variables

-

-

40

Minutes

3

Time to complete a network variable update between two FieldServers
(acknowledged service)

-

40

-

Milli-
seconds

4

Time to complete a network poll message between two FieldServers
(request/response service)

-

125 -

Milli-
seconds

5

Time to complete a network management variable fetch message
between two FieldServers (request/response service)

-

125 -

Milli-
seconds

Advertising