Field Controls UV-AIRE UV-E User Manual

Page 2

Advertising
background image

page 2

WARNING:

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.

Never operate the UV-Aire Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

INSTALLATION

Determine a suitable location on either the supply or

1.

return for the unit as shown in Figure 1. The unit must be

mounted at least 3 feet from any flex duct type material.

NOTE:

Unit can only be mounted in a vertical position as

noted on inside cover label.

Apply mounting template to air duct. (See Figure 2)

2.

Drill

3.

1

8

" diameter mounting holes at positions indicated on

template. (See Figure 2)
Using a 2" hole saw, drill out lamp hole as shown on

4.

template. (See Figure 2)
Drill a

5.

7

8

" inspection hole as shown on template.

(See Figure 2)
Remove template.

6.

Mount unit to duct using the 4 supplied sheet metal screws.

7.

(See Figure 3)

Lamp Length

Minimum

Duct

Width

Volts

Amps

Hz Watts

Max Air

Temp ºF

Lamp Intensity at

1 meter

Recommended

Max Sq. Feet

12"

9

120/240

.5

60

30

150º

37µW/cm

2

1500

18"

14

120/240

.5

60

30

150º

73µW/cm

2

2000

28"

22

120/240

1.1

60

60

150º

105µW/cm

2

3000

Figure 1

Figure 3

Figure 2

GENERAL INFORMATION
This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or

condition, nor for use in the mitigation, treatment, or prevention of any disease or condition.

There are different size units available, depending on the square footage of your home. See chart below for

determining your home’s needs.

WARNING:

Before installing or servicing a humidifier, air filter, heat system, or this unit, etc., always

turn all power OFF and have units unplugged. Electrical shock can cause personal injury or death.

Never expose eyes or skin to direct UVC light from any source.