Product specifications – Fedders AFPB36A1 User Manual

Page 3

Advertising
background image

Product Specifications

3

Specifications subject to change without notice.

Specifications applicable to upflow and horizontal applications.
Air flow shown at the following conditions:

- No heat elements in Air Handler. Decrease CFM 2% for 5 kW, 7.5 kW or 10 kW heat kits. Decrease CFM 1% for 15 kW or 20 kW heat kits.
- 60 Hertz – 230 volts. Decrease CFM 6% for 208 volt operations.
- Dry coil airflow shown.

AIRFLOW PERFORMANCE

MODEL

NUMBER

BLOWER

SPEED

MEASURED STATIC PRESSURE INLET TO OUTLET

(INCHES WATER COLUMN)

0.20

0.30

0.40

0.50

0.60

AFPB24A1

HIGH

925

900

850

795

690

MEDIUM

800

760

745

670

N/A

LOW

655

625

600

N/A

N/A

AFPB24B1

HIGH

905

880

830

780

680

MEDIUM

785

735

730

655

N/A

LOW

645

615

590

N/A

N/A

AFPB36A1

HIGH

1440

1350

1260

1180

1040

MEDIUM

1300

1220

1050

940

860

LOW

1160

1070

950

880

780

AFPC48A1

AFPC48B1

HIGH

1680

1640

1590

1520

1430

MEDIUM

1440

1410

1380

1340

1250

LOW

1240

1220

1190

1150

1100

AFPC60A1

AZFPC60B1

HIGH

2230

2105

1990

1895

1725

MEDIUM

1950

1930

1840

1770

1590

LOW

1360

1360

1350

1340

1080

Advertising