1 using the auto/off/manual switch (figure 3.1), 2 automatic transfer operation, 1 “auto” position – Generac Power Systems 005240 User Manual

Page 18: 2 “off” position, 3 “manual” position, 4 choke operation, Figure 3.1 – generator control panel

Advertising
background image

16

Figure 2.5 – Voltage Adjustment Potentiometer

Turn to
adjust voltage.

3.1

USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 3.1)

3.1.1 “AUTO”

POSITION

Selecting this switch position activates fully automatic
system operation. It also allows the unit to automati-
cally start and exercise the engine every seven days
with the setting of the exercise timer (see the Setting
the Exercise Timer section).

3.1.2 “OFF”

POSITION

This switch position shuts down the engine. This
position also prevents automatic operation.

Figure 3.1 – Generator Control Panel

OFF

EXERCISE

SYSTEM FUSE

15A

ASSY: 0F8418/0F8419

SET

TIME

AUTO.

MAN.

NO UTILITY SENSE
5 FLASHING RED LEDS=
EXERCISER NOT SET

FLASHING GREEN LED=

SYSTEM SET

NO RPM SENSE IF FLASHING

OVER SPEED

CONTROL AND INFORMATION CENTER

LOW BATTERY

LOW OIL

HIGH TEMP

OVER CRANK

‹

‹

3.1.3 “MANUAL”

POSITION

Set the switch to MANUAL to crank and start the
engine. Transfer to standby power will not occur
unless there is a utility failure.

With the switch set to AUTO, the engine may

crank and start at any time without warning.
Such automatic starting normally occurs when
utility power source voltage drops below a pre-
set level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch to
OFF and remove the fuses before working on or
around the generator or transfer switch. Then,
place a “DO NOT OPERATE” tag on the genera-
tor panel and on the transfer switch.

3.1.4 CHOKE

OPERATION

1. 990 engines have an electric choke in the air box

that is automatically controlled by the electronic
control board.

2. 530 engines have an electric choke on the divider

panel air inlet hose that is automatically con-
trolled by the electronic control board.

3. 410 engines do not have a choke.

3.2

AUTOMATIC TRANSFER
OPERATION

To select automatic operation, do the following:

1. Make sure the transfer switch main contacts are

set to their UTILITY position, i.e., loads con-
nected to the utility power source (Figure 3.2).

2. Be sure that normal UTILITY power source volt-

age is available to transfer switch terminal lugs
N1 and N2 (Refer to the Electrical Data section).

3. Set the generator’s AUTO/OFF/MANUAL switch to

AUTO.

4. Set the generator’s main circuit breaker to its ON

(or CLOSED) position.

With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to the
Sequence of Automatic Operation section.

‹

‹

Section 3 — Operation

Air-cooled Generators

Advertising
This manual is related to the following products: