Centrifugal Utility Fans

Installation

Inspect the unit for any damage and report it to
the shipper immediately. Also, check to see that all
accessory items are accounted for.

Move the fan to the desired location and fasten
securely through mounting holes provided in the base
angles. The unit must be set level (shimming may be
necessary). Flexible duct connections and vibration
isolators should be used where noise is a factor.

The motor voltage and ampere rating must be
checked for compatibility with the electrical supply
prior to final electrical connection. Supply wiring to the
fan must be properly fused, and conform to local and
national electrical codes.

The discharge is factory set as specified by customer
order, however, it can be rotated to other discharge
positions in the field if necessary. Removal of the
housing bolts allows the discharge to be rotated to
the clockwise positions below. For TAD, BD and BAD
discharge positions, a portion of the frame angle must
be removed.

Clockwise rotation shown. Counterclockwise
discharge positions are a mirror image of those
shown. Fan rotation is always specified from the
drive side of the housing.

Affect of Installation on Performance

Restricted or unstable flow at the fan inlet can cause
pre-rotation of incoming air or uneven loading of the
fan wheel, yielding large system losses, increased
sound levels and structural failure of the fan wheel.
Free discharge or turbulent flow in the discharge
ductwork will also result in system effect losses.

The examples below show the system layout and
inlet and discharge configurations which can affect
fan performance.

GOOD

POOR

POOR

FAIR

7

o

MAX.

POOR

FAIR

POOR

FAIR

One

Impeller

Dia.

GOOD

Should be at least
1/2 Impeller Dia.

FAIR

Not Greater than
60

o

Including Angle

POOR

POOR

FAIR

GOOD

POOR

Turning

Varies

CW BH

CW BAU

CW TAU

CW UB

CW TH

CW TAD

CW BAD

CW DB

Discharge Positions

Discharge Configurations

®