Caution, Warning – Goodman Mfg A/GPG13 M User Manual

Page 7

Advertising
background image

7

P

IPING

IMPORTANT NOTE: To avoid possible unsatisfactory operation or
equipment damage due to under firing of equipment, do not un-
dersize the natural/propane gas piping from the meter/tank to the
unit. When sizing a trunk line, include all appliances on that line
that could be operated simultaneously.
The rating plate is stamped with the model number, type of gas
and gas input rating. Make sure the unit is equipped to operate on
the type of gas available. The gas line installation must comply
with local codes, or in the absence of local codes, with the latest
edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.

Natural Gas Connection

Length of

Pipe in Feet

1/2

3/4

1

1 1/4

1 1/2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based

on 0.60 Specific Gravity Gas)

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Nominal Black Pipe Size (inches)

B T U H F urnace Inp ut

H eatin g V alu e of G as (B T U /C ub ic F o ot)

C F H =

Refer to the Proper Piping Practice drawing for the general layout
at the unit. The following rules apply:

1. Use black iron pipe and fittings for the supply piping. The

use of a flex connector and/or copper piping is permitted
as long as it is in agreement with local codes.

2. Use pipe joint compound on male threads only. Pipe joint

compound must be resistant to the action of the fuel used.

3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter

the gas valve. The drip leg must be a minimum of three
inches long.

5. Use two pipe wrenches when making connection to the gas

valve to keep it from turning.

6. Install a manual shut-off valve in a convenient location

(within six feet of unit) between the meter and the unit.

7. Tighten all joints securely.
8. The unit must be connected to the building piping by one

of the following methods:

Rigid metallic pipe and fittings

Semirigid metallic tubing and metallic fittings (Aluminum
alloy tubing must not be used in exterior locations)

Listed gas appliance connectors used in accordance with
the terms of their listing that are completely in the same
room as the equipment

In the prior two methods above the connector or tubing
must be protected from physical and thermal damage.
Aluminum alloy tubing and connectors must be coated to
protect against external corrosion when in contact with
masonry, plaster or insulation or are subject to repeated
wettings by liquids (water - not rain water, detergents or
sewage)

DRIP LEG

MANUAL
SHUT-OFF
VALVE

GROUND JOINT UNION
(INSTALLED AHEAD OF GAS VALVE)

GROMMET

Proper Piping Practice

NOTE: The unit gas supply entrance is factory sealed with plugs.
Keep plugs in place until gas supply is ready to be installed. Once
ready, replace the plugs with the supplied grommets and install gas
supply line.

G

AS

P

IPING

C

HECKS

CAUTION

T

O PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE

FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS

CONNECTIONS AND PRESSURE TESTING:

T

HE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE

PLACING IN OPERATION.

B

ECAUSE OF THE DANGER OF EXPLOSION OR

FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

N

EVER

EXCEED SPECIFIED PRESSURES FOR TESTING.

H

IGHER PRESSURE MAY

DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN

PREMATURE HEAT EXCHANGE FAILURE.

T

HIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM

THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT

TEST PRESSURES IN EXCESS OF 1/2

PSIG

(3.48 K

P

A).

T

HIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY

CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE

TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES

EQUAL TO OR LESS THAN 1/2

PSIG

(3.48 K

P

A).

WARNING

T

O AVOID PROPERTY DAMAGE OR PERSONAL INJURY

, BE SURE THERE IS

NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.

There will be air in the gas supply line after testing for leaks
on a new installation. Therefore, the air must be bled from the
line by loosening the ground joint union until pure gas is
expelled. Tighten union and wait for five minutes until all gas
has been dissipated in the air. Be certain there is no open
flame in the vicinity during air bleeding procedure. The unit is
placed in operation by closing the main electrical disconnect
switch for the unit.

Advertising