COMMERCIAL 60 kW

KW RATING

60

ENGINE SIZE

3.0 Liter V-6

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

60

250

300

120/208V, 3-phase, 0.8 pf

60

208.4

250

120/240V, 3-phase, 0.8 pf

60

180.6

200

277/480V, 3-phase, 0.8 pf

60

90.3

100

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase

120

480V

3-phase

141

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft

3

/hr.) (gal/hr.)

cu

ft/hr

Exercise

cycle

123

1.34

48.7

25% of rated load

260

2.84

103.3

50% of rated load

500

5.46

198.6

75% of rated load

700

7.64

277.9

100% of rated load

960

10.48

381.3


ENGINE COOLING
Air

flow

(inlet air including alternator and combustion air)

ft

3

/min. 3,280

System coolant capacity

US gal.

2.5

Heat rejection to coolant

BTU/hr.

270,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

180


SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode

63

db(A) @ 23 feet at normal operating load

71


EXHAUST
Exhaust flow at rated output 60 Hz

cfm 494

Exhaust temp. at muffler outlet

°F

1,050

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

3600

HP at rated KW

60 Hz

94

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature

Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude

Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

COMMERCIAL 60 kW

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance
with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient
temperature, altitude, engine power and condition, etc.