Servicing instructions, Servicing / fault finding charts, Ignition functional check 1 – Stovax 5 User Manual

Page 14: Servicing requirements

Advertising
background image

14

IGNITION FUNCTIONAL CHECK 1

PILOT WILL NOT LIGHT

Ensure there is no debris around the pilot assembly,

(e.g. soot, etc.) which could short the spark, clean the area.

Operate the valve.

Is there a spark?

Consult Section

2 and retry.

Check alignment of pilot

burner head, change the

ignition lead,

see diagram 1 on page 17.

Check isolation tap and

gas meter, retry.

Correct and

retry.

Purge the gas pipes

and retry.

SEE 'NO SPARK'

CHART

SYSTEM OK

There is a blockage in the system, check the inlet test point,

the mag seating, valve and pilot filter.

Is the gas turned on to the

appliance?

Is the gas pressure correct?

Has the system got

any air in it?

Does the pilot light?

Is the control being

operated correctly?

Will the pilot light

with a match?

No

Yes

No

Yes

No

Yes

Yes

No

No

Yes

No

No

Yes

Yes

SERVICING INSTRUCTIONS

SERVICING / FAULT FINDING CHARTS

This appliance must be serviced at least once a year by a
competent person.
All tests must be serviced by best practice as described by
the current CORGI recommendations.

1.1

Before any test are undertaken on the appliance, conduct a
gas soundness test for the property to ensure that there are
no gas leaks prior to starting work.

1.2

Before any tests are undertaken on the applaince it is also
recommended to fully check the operation of the
appliance.

1.3

Special checks
1.3.1 Clean any lint or fluff from the pilot - pay particular

attention to the aeration hole in the side of the pilot

1.3.2 Clean away any fluff or lint from under the burner
1.3.3 Check that the spark gap on the pilot is correct

1.4

Correct any faults found during the initial tests and then re-
commission the appliance conducting the usual safety
checks.

1.5

Advise the customer of any remedial action taken.

1. SERVICING REQUIREMENTS

AR0097

3.5mm

15mm

Advertising