PeCifiCaTions

GPG1336

090M43A*

GPG1348

090M43A*

GPG1360

090M43A*

Cooling Capacity
Total BTU/h

36,000

46,000

56,500

Sensible BTU/h

27,800

36,700

43,800

SEER / EER

13.0 / 11.0

13.0 / 11.0

13.0 / 10.6

Decibels

78

80

80

AHRI #s

4385095

4385098

4385100

Heating Capacity
Input BTU/h

92,000

92,000

92,000

Output BTU/h

73,600

73,600

73,600

AFUE

80

80

80

Temperature Rise Range

45 - 75

45 - 75

45 - 75

No. of Burners

4

4

4

Orifice Size (Natural/Propane)

43/ 55

43/ 55

43 / 55

Evaporator Motor / Coil
Type

DD

X-13

X-13

Wheel (D x W)

10” x 9”

11” x 10”

11” x 10”

Indoor Nominal CFM

1,200

1,550

1,750

Motor Speed Tap (Cooling)

low

T4

T4

RPM/Amps (Cooling)

910/3.06

1050/5.8

1,050/7.4

Horsepower

¾”

1.0

Face Area (ft²)

5.67

5.67

5.67

Rows Deep/ Fins per Inch

4/ 14

4/ 14

4/ 14

Piston Size (Cooling)

0.068

0.076

0.087

Filter Size (ft²)

4.2

5.1

6.3

Drain Size (NPT)

¾”

¾”

¾”

Refrigerant Charge (oz.)

110

125

185

Condenser Fan
Horsepower - RPM

¼ - 830

¼ - 1,075

¼ - 1,100

Fan Diameter/ # of Fan Blades

22” / 3

22” / 3

22” / 3

Outdoor Nominal CFM

3,500

3,500

3,250

Coil
Face Area (ft²)

15.4

15.4

15.4

Rows Deep/ Fins per Inch

1/ 24

1/ 24

1/ 24

Compressor
Quantity / Type

1 / Scroll

1 / Scroll

1 / Scroll

Stage

Single

Single

Single

Compressor RLA/LRA

10.4/73.0

13.1/83.1

16.0/ 134

Electrical Data
Voltage-Phase-Frequency

208/230-3-60

208/230-3-60

208/230-3-60

Indoor Blower FLA/ LRA

3.06/ 4.1

5.8

7.4

Outdoor Fan RLA/ LRA

1.5 / 3.0

1.4/ 2.9

1.4/ 2.9

Total Unit Amps

15

20.3

24.8

Min. Circuit Ampacity

17.6

23.6

29

Max. Overcurrent Protection

25 amps

35 amps

45 amps

Entrance Size Power Supply

1⅛”

1⅛”

1⅛”

Entrance Size Control Voltage

⅞”

⅞”

⅞”

Operating Weight (lbs)

490

523

533

Ship Weight (lbs)

513

545

555

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

² Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.