System operation – Goodman Mfg R-410A User Manual

Page 18

Advertising
background image

18

SYSTEM OPERATION

Dip Switch Number

Function

1
2
3

N/A

4

Indoor Thermostat

5
6
7
8

Cooling & Heat Pump CFM

CFM Trim Adjust

Electric Heat

Table 1

CFM Delivery
Tables 2 and 4 show the CFM output for dip switch combi-
nations 1-2 (Electric Heat), and 5-6 (Cooling/Heating).

Tables 3 shows the dip switch settings for 1 and 2-stage
thermostats.

Model

Switch 1

Switch 2 Electric Heat CFM

OFF

OFF

1050

(F)

ON

OFF

950

OFF

ON

825

ON

ON

700

OFF

OFF

1250

(F)

ON

OFF

1100

OFF

ON

1000

ON

ON

800

OFF

OFF

1800

(F)

ON

OFF

1700

OFF

ON

1400

ON

ON

1225

OFF

OFF

2000

(F)

ON

OFF

1800

OFF

ON

1600

ON

ON

1400

APH1536

APH1548

APH1524

APH1560

(F)

Factory

Table 2

Model

Switch 3

Switch 4

Thermostat

N/A

ON

1-Stage

N/A

OFF

2-Stage

APH15**

Table 3

Model

Switch 5

Switch 6

Cooling/HP CFM

OFF

OFF

1050

(F)

ON

OFF

950

OFF

ON

825

ON

ON

700

OFF

OFF

1250

(F)

ON

OFF

1100

OFF

ON

1000

ON

ON

800

OFF

OFF

1800

(F)

ON

OFF

1700

OFF

ON

1400

ON

ON

1225

OFF

OFF

2000

(F)

ON

OFF

1800

OFF

ON

1600

ON

ON

1400

APH1536

APH1548

APH1524

APH1560

(F)

Factory

Table 4

Thermostat “Fan Only” Mode
During Fan Only Operations, the CFM output is 30% of the
high stage cooling setting.

CFM Trim Adjust
Minor adjustments can be made through the dip switch com-
bination of 7-8. Table 5 shows the switch position for this
feature.
NOTE: The airflow will not make the decreasing adjustment
in Electric Heat mode.

CFM

Switch 7

Switch 8

+10%

ON

OFF

Normal

OFF

OFF

-15%

OFF ON

Table 5

Humidity Control
When using a Humidistat (normally closed), cut jumper PJ6
on the control board. The Humidistat will only affect both low
stage and high stage cooling airflow by adjusting the Airflow
to 85%.

Two Stage Heating
When using staged electric heat, cut jumper PJ4 on the con-
trol board.

Thermostat Wiring
Use thermostat wiring diagrams provided with the thermostat
when making these connections.

See Specification Sheet for APH model series for CFM vs
ESP tables.