Operating data – Generac Power Systems Guardian Elite 05402 User Manual

Page 3

Advertising
background image

STANDBY 30 kW

KW RATING

30 LP / 29 NG

ENGINE SIZE

1.6 Liter 4 cyl. inline

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

30 LP / 29 NG

125 LP / 120.8 NG

150

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%

single phase

56

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft

3

/hr.) (gal/hr.)

cu

ft/hr

Exercise

cycle

60

0.65

24

25% of rated load

193

2.1

76

50% of rated load

300

3.3

120

75% of rated load

415

4.5

165

100% of rated load

525

5.7

209


ENGINE COOLING
Air

flow

(inlet air including alternator and combustion air)

ft3/min. 1,800

System coolant capacity

US gal.

2.0

Heat rejection to coolant

BTU/hr.

131,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

95


SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode

62

db(A) @ 23 feet at normal operating load

75


EXHAUST
Exhaust flow at rated output 60 Hz

cfm 260

Exhaust temp. at muffler outlet

°F

1025

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

3600

HP at rated KW

60 Hz

48

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

STANDBY 30 kW

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1.
Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuelBtu content, ambient temperature, altitude,
engine power and condition, etc.

Advertising