24

GE Zenith Controls

ZTG/ZTGD Operation and Maintenance Manual (70R-1000D)

Troubleshooting and Diagnostics

HAZARDOUS VOLTAGES CAN CAUSE SEVERE INJURY OR DEATH.

These charts may indicate problems that require authorized GE Zenith service personnel.

Hazardous voltages may exist on termination plugs other than those that go into the MX150.

Symptom

Annunciation

Possible Cause(s)

Corrective Action

Engine does not START

SOURCE 2
AVAILABLE
LED off

Engine start wires not
terminated properly

Check engine start connections

Engine does not stop

LCD Display -
“TD Engine Cool Down”

SOURCE 1 POSITION, and
SOURCE 1 and SOURCE 2
AVAILABLE LEDs on,
but U timer has timed out

U timing cycle not complete

Engine start wires not
terminated correctly

Generator in MANUAL

Check U timer setting

Check Engine Start Connections

Place generator in AUTO

ATS will not transfer
to SOURCE 2

SOURCE 2 AVAILABLE
LED off

None

SOURCE 2 voltage or frequency
not within acceptable parameters

Power supply connector unplugged

Check: Engine Start Connections,
Generator Breaker, Generator Output,
and Engine Control Switch

Plug in connector

ATS will not transfer
to SOURCE 1

SOURCE 1 AVAILABLE
LED off

None

SOURCE 1 voltage or frequency
not within acceptable parameters

Power supply connector unplugged

Check utility and utility breakers

Plug in connector

General Troubleshooting

The following troubleshooting guide is used to recognize,
and determine basic faults. When using this guide, it will
ask several questions about the condition of the switch.
This guide will then list an order of the possible faults.
You will then look at the first suspected fault to determine
if it is the problem. If it is not a fault, you go to the
second suspected fault. If you go through all of the

Generator is in OFF position

Investigate why Engine Control
Switch was turned off

LCD Display -
“S1 _ _ _ _ TD XFR S1>S2
Time Remaining _ _ _ _”

W timing cycle not complete

Check W Timer setting

LCD Display -
“Diagnostic Code 001”

LCD Display -
“S1 OK
Time Remaining _ _ _ _

Bypass”

Limit switch or RT box
connector unplugged

T timing cycle not complete

Call Technical Services

Check T Timer setting

LCD Display -
“ATS Open
Time Remaining _ _ _ _”

DW timing cycle not complete

Check DW Timer setting

ZTG Series

LCD Display -
“ATS Open
Time Remaining _ _ _ _”

TD timing cycle not complete

Check DT Timer setting

ZTGD Series

DANGER

suspected faults, or the chart instructs you to, call
a GE Zenith Representative for further assistance.

NOTE

: When you use the troubleshooting charts,

the Annunciation column refers to the

LED

’s on

the control panel.