1 control console components, 2 manual transfer and start-up, Danger – Generac 005030-0 (15kW) User Manual

Page 17: 1 auto/off/manual switch, 2 fault indicator leds, 3 15 amp fuse, 4 5 amp fuse, 5 set exercise time switch, 6 system ready led, Figure 3.1 - generator control console

Advertising
background image

15

Section 3 - Operation

Liquid-cooled 15, 20 and 25 kW Generators

3.1

CONTROL CONSOLE
COMPONENTS

The components of a home standby generator control
console (Figure 3.1) are as follows:

Figure 3.1 - Generator Control Console

3.1.1 AUTO/OFF/MANUAL SWITCH

Use this three-position switch as follows:

• Set the switch to AUTO for fully automatic opera-

tion. See “Automatic Operation” (Section 3.6).

• Set switch to MANUAL position to crank and start

the generator engine.

• Set switch to OFF position to shut down an oper-

ating engine. With OFF selected, operation will not
be possible.

With switch set to AUTO, engine can crank and
start suddenly without warning. Such automat-
ic start up normally occurs when utility source
voltage drops below a pre-set level. To prevent
possible injury that might be caused by such
sudden starts, set AUTO/OFF/ MANUAL switch
to OFF before working on or around the unit.
Then, place a “DO NOT OPERATE” tag on con-
trol console.

3.1.2 FAULT INDICATOR LEDS

(SEE CHART ON PAGE 16)

These red LEDs turn ON when one or more of the fol-
lowing engine faults occurs and the engine shuts
down.

• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/Engine Speed Signal Fault
• High Coolant Temperature/Low Coolant Level

See Section 1.7 for further explanation of engine pro-
tection functions.

3.1.3 15 AMP FUSE

This fuse protects the control console’s DC control
circuit against electrical overload and is located
inside the control panel. If the fuse has melted open
because of an overload, engine cranking and startup
cannot occur. If the fuse needs to be replaced, use
only an identical 15-amp replacement fuse (type
ATO).

3.1.4 5 AMP FUSE

This fuse protects the battery charger against electri-
cal overload and is located inside the control panel. If
the fuse needs to be replaced, use only an identical 5-
amp replacement fuse (type ATO).

NOTE:

This fuse will not remove the + battery input
power from the PCB when it opens. This means
the exercise timer will not be reset.

3.1.5 SET EXERCISE TIME SWITCH

This switch allows programming the generator to
start and exercise automatically. “See Weekly
Exercise Cycle” (see Figure 3.3 and Section 3.6).

3.1.6 SYSTEM READY LED

The System Ready LED (green) has two main pur-
poses. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.

The system ready LED will be OFF when the switch
is in the MANUAL or OFF positions.

The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.

This secondary function is only available with DIP
switch two in the OFF position (ATS - automatic
transfer switch application).

3.2

MANUAL TRANSFER AND
START-UP

To transfer electrical loads to the Standby (EMER-
GENCY) power source side and start the engine man-
ually, refer to the Owner’s Manual of the particular
transfer switch.

‹

‹

‹

‹

‹

!

DANGER

‹

CAUTION

RISK OF ELECTRICAL SHOCK. DO NOT REMOVE COVER. NO USER SERVICEABLE

PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.

CAUTION

FOR STAND-BY SERVICE CONNECT OUTPUT OF GENERATOR TO SUITABLY RATED
TRANSFER SWITCH IN ACCORDANCE WITH CANADIAN ELECTRICAL CODE, PART I.

TENTION: POUR L'ALIMENTATION DE RESERVE, CONNECTER LA SORTIE DE
ATRICE A UN COMMUTATEUR DE CALIBRE APPROPRIE, CONFORMENENT AU

CANADIEN DE L'ECTRICITE, PREMIERE PARTIE.

WARNING

CAN AUTOMATICALLY START AT ANYTIME WITHOUT NOTICE.

Y REMOVE FUSE ON CONTROL PANEL AND NEGATIVE BATTE

SERVICING.

WARNING

THIS EMERGENCY POWER SYSTEM IS DESIGNED EXCLUSIVELY FOR

OUTDOOR INSTALLATION ONLY!

0E7193

USE OF SYNTHETIC OIL IS RECOMMENDED

ON

0F2629

THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.

MANUAL

SET

EXERCISE

TIME

TO SET EXERCISER TIME

2) HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS
AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)
THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS

1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

OVER SPEED

OVER CRANK

LOW BATTERY

SYSTEM READY

AUTO

OFF

FLASHING GREEN LED = NO UTILITY SENSE
5 FLASHING RED LED'S = EXERCISER NOT SET

LED INDICATORS:

RED LED'S = INDIVIDUAL FAULT

(IN AUTO MODE ONLY)

OFF

HI COOL. TEMP.

LOW COOL. LEVEL

LOW OIL PRESS.

(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)

SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON