Operating data – Generac Power Systems SG020 User Manual

Page 3

Advertising
background image

STANDBY

SG020

SG025

GENERATOR OUTPUT VOLTAGE/KW-60Hz

NG/LP

Rated AMP

NG/LP

Rated AMP

120/240V, 1-phase, 1.0 pf

20

83.3

25

104.2

120/208V, 3-phase, 0.8 pf

20

69.5

25

86.8

120/240V, 3-phase, 0.8 pf

20

60.2

25

75.3

277/480V, 3-phase, 0.8 pf

20

30.1

25

37.6


MOTOR STARTING KVA
Maximum at 35% instantaneous voltage dip

with standard alternator; 60 hz

40

46


FUEL

Fuel consumption—60 hz—100% Load

N.G.

L.P.

N.G.

L.P.

ft.

3

/hr.

369

153

442

183

m

3

/hr.

10.4

4.3

12.5

5.2


COOLING
Coolant capacity

System lit.(US gal.)

6.6 (2)

6.6 (2)

Engine lit.(US gal.)

0.9 (0.25)

0.9 (0.25)

Radiator lit.(US gal.)

6.6 (1.75)

6.6 (1.75)

Coolant flow/min.

60 hz lit.(US gal.)

40 (10.6)

40 (10.6)

heat rejection to coolant

60 hz BTU/hr.

96,000

120,000

Cooling air flow

60 hz m

3

/min. (cfm)

45 (1590)

45 (1590)


COMBUSTION AIR REQUIREMENTS
Flow at rated power

60 hz m

3

/min. (cfm)

1.8 (65)

2.3 (81)

EXHAUST
Exhaust flow at rated output

60 hz m

3

/min. (cfm)

6.0 (212)

7.3 (260)

Max. recommended back pressure

Kpa (hg)

5.0 (1.5")

5.0 (1.5")

Exhaust temp. at rated output

o

C (

o

F)

593 (1100)

635 (1175)

Exhaust outlet size

N.P.T. (female)

1.5"

1.5"

ENGINE
Rated RPM

60 hz

3600

3600

hP at rated KW

60 hz

30

37

Piston speed

60 hz m/min. (ft./min.)

590 (1937)

590 (1937)

BMEP (psi)

60 hz - psi

78

97

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature

-3% for every 10

o

C above - °C

40

25

-1.5% for every 10

o

F above - °F

104

77

Altitude

-3% for every 300 m above - m

913

150

-3% for every 1000 ft. above - ft.

3000

500

OPERATING DATA

SG020 / SG025

Advertising
This manual is related to the following products: