Operating data – Generac Power Systems Guardian QT02224 User Manual

Page 3

Advertising
background image

QT022

kW RATING

22

ENGINE SIZE

2.4 Liter Inline 4

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/208V, 3-phase, 0.8 pf

22

76

100

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208 3-phase

43

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft

3

/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

42

0.44

16

25% of rated load

100

1.0

38

50% of rated load

190

2.0

98

75% of rated load

255

2.7

98

100% of rated load

316

3.3

120

ENGINE COOLING
Air flow

(inlet air including alternator and combustion air)

ft

3

/min.

2,400

System coolant capacity

US gal.

2.5

Heat rejection to coolant

BTU/hr.

99,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

68


SOUND EMISSIONS IN DBA
Exercising at 7 meters

61

Normal operation at 7 meters

70

EXHAUST
Exhaust flow at rated output 60 Hz

cfm

165

Exhaust temp. at muffler outlet

°F

900

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

1800

HP at rated KW

60 Hz

40

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

ENCLOSURE
Material

Aluminum

Color

PMS 422 (Bisque)

OPERATING DATA

QT022

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.