Application & Design

An electro-pneumatic (EP) switch, also known as a three way solenoid valve, is used to electrically open and close a pneumatic
actuated damper. It is wired in series with a normally closed thermostat when used with a fire smoke damper (FSD) to initiate
closure at elevated temperatures. The EP switch can also be used on a smoke damper (SMD) to initiate closure when required in
a smoke control system.

Assembly

9

7

3

2

1

6

4

5

8

input signal: 24 Vdc

(specify) 24 Vac

120 Vac

item Qty. part # Description

Kit #

1

1

-

Valve

1

8

" NPT

2

1

-

Retaining Clip

3

1

452460 S/V 120 Vac

812441

-

1

380913 S/V 24 Vac

812442

-

1

381042 S/V 24 Vdc

812443

4

1

651371 Mounting Bracket

5

1

380850 2 x 4 x 1.875 Ext. Box

6

2

415555 #10 x 0.50 TEK Screw

7

1

380257 2 x 4 Blank Cover

8

1

415539 #10-32 HH Grounding

Screw (green)

9

1

454850 Label

Kit #s include appropriate voltage solenoid valve shown
under Item 3 and all other Item #s above.

Port 3
Exhaust

Port 2
Supply

Port 1
To Actuator

ASCO Solenoid
Va lve Assembly

Red

Red

TOR/RRL
Wiring
Har dware

Solenoid Va lve With TOR

Solenoid Valve

TOR

Brown
Orange
Black
Blue
Red

Purple
Yellow

Red

Red

Orange

Black

Solenoid Va lve With RRL

Solenoid Valve

RRL

Red

Red

typical setup