Standby Power Rating Prime Power Rating

350 KW 60 Hz 280 KW 60 Hz

n The Generac Modular Paralleling system utilizes

multiple small generators in a side by side parallel
arrangement to achieve a larger combined power
output.

n The proven 13.3 liter Generac generators can be

combined up to 10 units to provide from 300 kW to 1
megawatts of reliable power.

n Paralleling System Features. The paralleling function is

controlled by Generac’s field proven Power Manager
Control utilizing contractor switching technology
resulting in cost effective reliable paralleling. The MPS
control system provides automatic synchronization,
adjustable load sharing between generators, reverse
power protection and load shedding contacts.

n The optional cable interconnect cabinet is furnished with

bus bar and lugs to allow easy cabling between the
multiple gensets. Recommended for 3 or more gensets.

n The Generac “Power Manger Generator controller”

provides complete engine monitoring and control along

with alarm function and communication ability via a
RS232 with a modem link to Generac’s Genlink
software or Modbus control. A RS485 link is also
available.

n Flexibility. The Modular Power systems flexibility allows

for a wide variety of configurations, including single or
multiple automatic transfer switch arrangements roof
application where better weight distribution is required
and areas with specific height or depth limitations.
Since MPS gensets need not be located together, space
can be utilized wherever it is available. Smaller units
are also easier to transport and place on the jobsite.

n Redundancy. N+1 means greater reliability with MPS.

Backup power during scheduled maintenance.
Simplified service which reduces maintenance costs.

n Single source service response from Generac’s dealer

network provides parts and service support for the entire
unit. You are never on your own when you own a
Generac Power System

GEN

Diesel Generator

Circuit
Breaker

Contactor

Contactor

Diesel Generator

Circuit
Breaker

GEN

Transfer Sw

W/ Integral

Control

UTILITY

Distribution
Cab

Contactor

Diesel Generator

Contactor

Circuit
Breaker

Circuit
Breaker

Diesel Generator

GEN

GEN

UTILITY

ATS

UTILITY

ATS

Distribution
Cab

Distribution
Cab

PMSC

Controller

Cabinet

Control Wires

Power Manager Integrated Controller Layout Power Manager System Controller Layout

FEATURES

Modular Power
System (MPS)

Powered with Generac’s 13.3 Natural Gas Engine

MPSG350

350 kW

®

Advertising