The normal operational sequence in heating mode is as fol-
lows:

•

R and W1 (or R and W1/W2) thermostat contacts close,
initiating a call for heat.

•

Integrated control module performs safety circuit checks.

•

Induced draft blower is energized on high speed for a 15-
second prepurge. Humidifier terminal is energized with
induced draft blower.

•

Induced draft blower steps to low speed following
prepurge. Low stage pressure switch contacts are
closed.

•

Igniter warm up begins upon step to low speed and
presence of closed low stage pressure switch contacts.

LED LED

Status

Indication

Possible Causes

Corrective Action(s)

Notes & Cautions

Off

x Normal condition

x None

x None

x None

1 Flash

x Communications

Failure

x Communications

Failure

x Depress Learn Button
x Verify that bus BIAS

and TERM
dipswitches are in the
ON position.

x Depress once

quickly for a power-
up reset

x Depress and hold

for 2 seconds for
an out-of-box reset

Red

Communications

LED

2 Flashes

x Out-of-box reset

x Control power up
x Learn button

depressed

x None

x None

Off

x No power
x Communications

error

x No power to furnace
x Open fuse
x Communications error

x Check fuses and

circuit breakers;
replace/reset

x Replace blown fuse
x Check for shorts in

low voltage wiring in
furnace/system

x Reset network by

depressing learn
button

x Check data 1/ data 2

voltages

x Turn power OFF

prior to repair

1 Steady

Flash

x No network found

x Broken/ disconnected

data wire(s)

x Furnace is installed as

a legacy/ traditional
system

x Check

communications
wiring (data 1/ data 2
wires)

x Check wire

connections at
terminal block

x Verify furnace

installation type
(legacy/ traditional or
communicating)

x Check data 1/ data 2

voltages

x Turn power OFF

prior to repair

x Verify wires at

terminal blocks are
securely twisted
together prior to
inserting into
terminal block

x Verify data1 and

data voltages as
described above

Rapid

Flashing

x Normal network

traffic

x Control is “talking” on

network as expected

x None

x None

Green Receive

LED

On Solid

x Data 1/ Data 2

miss-wire

x Data 1 and data 2

wires reversed at
furnace, thermostat,
or CT™ compatible
outdoor AC/HP

x Short between data 1

and data 2 wires

x Short between data 1

or data 2 wires and R
(24VAC) or C (24VAC
common)

x Check

communications
wiring (data 1/ data 2
wires)

x Check wire

connections at
terminal block

x Check data 1/ data 2

voltages

x Turn power OFF

prior to repair

x Verify wires at

terminal blocks are
securely twisted
together prior to
inserting into
terminal block

x Verify data1 and

data voltages as
described above

N

ORMAL

S

EQUENCE

OF

O

PERATION

P

OWER

U

P

The normal power up sequence is as follows:

•

115 VAC power applied to furnace.

•

Integrated control module performs internal checks.

•

Integrated control module displays

88888 88888 on dual 7-segment

display LED’s.

•

Integrated control module monitors safety circuits
continuously.

•

Furnace awaits call from thermostat. Dual 7-segment
LED’s display

00000 PPPPP while awaiting call from thermostat.