Generac Power Systems 005012-1 User Manual

Page 21

Advertising
background image

19

• Batteries give off explosive hydrogen gas while

charging. The gas can form an explosive mixture
around the battery for several hours after charging.
Any spark, heat or flames can ignite the gas and
cause an explosion which can shatter the battery,
causing blindness or other serious injury.

4.6.3 BATTERY

MAINTENANCE

The battery should be inspected per the “Service
Schedule”. The following procedure should be fol-
lowed for inspection:

1. Inspect the battery posts and cables for tightness

and corrosion. Tighten and clean as necessary.

2. Check the battery fluid level of unsealed batteries

and, if necessary, fill with DISTILLED WATER
ONLY. DO NOT USE TAP WATER IN BATTER-
IES.

3. Have the state of charge and condition checked.

This should be done with an automotive-type bat-
tery hydrometer.

DANGER

Storage batteries give off explosive hydrogen

gas. This gas can form an explosive mixture
around the battery for several hours after charg-
ing. The slightest spark can ignite the gas and
cause an explosion. Such an explosion can shat-
ter the battery and cause blindness or other
injury. Any area that houses a storage battery
must be properly ventilated. Do not allow smok-
ing, open flame, sparks or any spark producing
tools or equipment near the battery.

Battery electrolyte fluid is an extremely caus-

tic sulfuric acid solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If the fluid is spilled, flush
the affected area immediately with clear water.

Do not use any jumper cables or booster battery

to crank and start the generator engine. If the
battery has completely discharged, remove it
from the generator for recharging.

‹

Be sure the AUTO/OFF/MANUAL switch is set to

the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.

Be sure the UTILITY power supply is turned OFF,

or sparking may occur at the battery posts as
the cables are attached and cause an explosion.

4.6.4 BATTERY

REPLACEMENT

When replacing batteries, use the same number and
the type of battery that follows:

NOTE:

The BCI number should be located directly on the
battery.

‹

Section 4 — Maintenance

40kW Liquid-cooled Generators

BCI Group No.

CCA

27F

700 @ 0 deg. F

PERIODIC REPLACEMENT PARTS

Part Name

Part Number

Oil Filter

# 0E7415

Radiator Cap #

046627

Air

Cleaner #

0A4637

Spark Plug Champion # RC12LC4

‹