Lfc coil dims – Greenheck Fan Low-Profile Fan Coil LFC User Manual

Page 6

Advertising
background image

6

Model LFC Low-Profile Fan Coil

®

Unit

Size

A

B

4 row

6 row

8 row

C

D

C

D

C

D

30

12.00 7.00 0.625 0.625 0.625 0.875 0.625 0.875

45

12.00 7.00 0.625 0.625 0.625 0.875 0.625 0.875

50

13.50 7.75 0.625 0.625 0.625 0.875 0.625 1.125

65

17.00 9.50 0.875 0.875 0.875 1.125 0.875 1.125

85

17.00 9.50 0.875 0.875 0.875 1.125 0.875 1.125

All dimensions are in inches.

Unit

Size

A

4 row

6 row

8 row

B

C

B

C

B

C

15

5.75

0.625 0.625 0.625 0.625 0.625 1.375

20

7.0

0.625 0.625 0.625 0.625 0.625 1.375

25

8.0

0.875 1.375 0.875 1.375 0.875 1.375

30

9.5

0.875 1.375 0.875 1.375 0.875 1.375

45

9.5

0.875 1.375 0.875 1.375 0.875 1.375

50

10.75 0.875 1.375 1.125 1.375 0.875 1.625

65

13.00 1.125 1.375 1.125 1.375 1.125 1.625

85

13.00 1.125 1.375 1.125 1.375 1.125 1.625

All dimensions are in inches.

NOTE

With airflow from left to right, the fluid enters the coil
from the bottom connection (Inlet) and exits from the
top (Outlet). The other two coil connections should
be capped off (Cap)

Chilled Water • 4, 6 or 8 Row

Unit Size

A

4 row

6 row

8 row

B

B

B

15

7.63

0.75

0.75

1.375

20

10.13

0.75

0.75

1.375

25

12.63

0.875

0.875

1.375

30

15.13

0.875

0.875

1.375

45

15.13

0.875

0.875

1.375

50

17.63

1.375

1.375

1.625

65

22.63

1.375

1.375

1.625

85

22.63

1.375

1.375

1.625

All dimensions are in inches.

A

3.75

2

1.5

B

Copper Sweat

0.75

1

Drain Connection

3

Outlet

Airflow

LFC-85

LFC-65

LFC-50

1.375

1.375

1.375

LFC-25

LFC-45

LFC-30

LFC-20

LCF-15

Unit Size

A

0.875

0.875

0.875

0.75

0.75

B (4 Row)

22.63

22.63

17.63

12.63

15.13

15.13

7.63

10.13

1.375

1.375

1.375

0.875

0.875

0.875

0.75

0.75

B (6 Row)

1.625

1.625

1.625

B (8 Row)

1.375
1.375
1.375
1.375
1.375

3.75

A

A

B

MSCF-20
MSCF-25
MSCF-30

Unit Size

MSCF-15

7.0

9.5

8.0

5.75

A

C (4 Row)

B (4 Row)

13.00
13.00

10.75

9.5

MSCF-45
MSCF-50
MSCF-65
MSCF-85

0.75

3

Outlet

1

Drain Connection

0.75

3

Outlet

1

Drain Connection

C (6 Row)

B (6 Row)

C (8 Row)

B (8 Row)

0.625
0.625
0.875
0.875
0.875
0.875
1.125
1.125

0.625
1.375

0.625

1.375
1.375
1.375
1.375
1.375

0.625
0.625
0.875
0.875
0.875
1.125
1.125
1.125

0.625
1.375

0.625

1.375
1.375
1.375
1.375
1.375

0.625
0.625
0.875
0.875
0.875
0.875
1.125
1.125

1.375
1.375
1.375
1.625
1.625
1.625

1.375
1.375

Chilled Water 4,6 or 8 Row

Direct Expansion (DX)-Single Circuit-4,6 or 8 Row

3.75

MSCF-30

Unit Size

12.00

A

D (4 Row)

C (4 Row)

17.00
17.00

13.50

12.00

MSCF-45
MSCF-50
MSCF-65
MSCF-85

D (6 Row)

C (6 Row)

D (8 Row)

C (8 Row)

0.625

0.875
0.875

0.625

0.875
0.875

0.625

0.875
0.875

0.875

1.125
1.125

0.625

1.125

Direct Expansion (DXI)-Dual Circuit with 50/50 Face

Interlaced Construction-4,6 or 8 Row

Airflow

Airflow

B

9.50

7.75

7.00

9.50

7.00

0.625

0.625

0.625

0.625

0.625

0.875

0.625

0.875

0.625

0.875

0.625

0.875

0.875
0.875

1.125
1.125

JOHNSONRI

03/13/2009

1/1

LFC COIL DIMS

B

Copper Sweat

C

Copper Sweat

C

Copper Sweat

D

Copper Sweat

2

1.5

2

1.5

0.25 vent and drain supplied. Right side connection shown.

NOTE

With airflow from left to right, the fluid enters the coil
from the center connection (Inlet) and exits from the
bottom (Outlet). The other coil connections should
be capped off (Cap).

Direct Expansion (DX) • Single Circuit • 4, 6 or 8 Row

Distributor hookup is done inside module through 2-inch access hole.

Right side connection shown.

A

3.75

2

1.5

B

Copper Sweat

0.75

1

Drain Connection

3

Outlet

Airflow

LFC-85

LFC-65

LFC-50

1.375

1.375

1.375

LFC-25

LFC-45

LFC-30

LFC-20

LCF-15

Unit Size

A

0.875

0.875

0.875

0.75

0.75

B (4 Row)

22.63

22.63

17.63

12.63

15.13

15.13

7.63

10.13

1.375

1.375

1.375

0.875

0.875

0.875

0.75

0.75

B (6 Row)

1.625

1.625

1.625

B (8 Row)

1.375
1.375
1.375
1.375
1.375

3.75

A

A

B

MSCF-20
MSCF-25
MSCF-30

Unit Size

MSCF-15

7.0

9.5

8.0

5.75

A

C (4 Row)

B (4 Row)

13.00
13.00

10.75

9.5

MSCF-45
MSCF-50
MSCF-65
MSCF-85

0.75

3

Outlet

1

Drain Connection

0.75

3

Outlet

1

Drain Connection

C (6 Row)

B (6 Row)

C (8 Row)

B (8 Row)

0.625
0.625
0.875
0.875
0.875
0.875
1.125
1.125

0.625
1.375

0.625

1.375
1.375
1.375
1.375
1.375

0.625
0.625
0.875
0.875
0.875
1.125
1.125
1.125

0.625
1.375

0.625

1.375
1.375
1.375
1.375
1.375

0.625
0.625
0.875
0.875
0.875
0.875
1.125
1.125

1.375
1.375
1.375
1.625
1.625
1.625

1.375
1.375

Chilled Water 4,6 or 8 Row

Direct Expansion (DX)-Single Circuit-4,6 or 8 Row

3.75

MSCF-30

Unit Size

12.00

A

D (4 Row)

C (4 Row)

17.00
17.00

13.50

12.00

MSCF-45
MSCF-50
MSCF-65
MSCF-85

D (6 Row)

C (6 Row)

D (8 Row)

C (8 Row)

0.625

0.875
0.875

0.625

0.875
0.875

0.625

0.875
0.875

0.875

1.125
1.125

0.625

1.125

Direct Expansion (DXI)-Dual Circuit with 50/50 Face

Interlaced Construction-4,6 or 8 Row

Airflow

Airflow

B

9.50

7.75

7.00

9.50

7.00

0.625

0.625

0.625

0.625

0.625

0.875

0.625

0.875

0.625

0.875

0.625

0.875

0.875
0.875

1.125
1.125

JOHNSONRI

03/13/2009

1/1

LFC COIL DIMS

B

Copper Sweat

C

Copper Sweat

C

Copper Sweat

D

Copper Sweat

2

1.5

2

1.5

NOTE

The first suction header on the entering air side of
the coil is circuited to the top distributor. With airflow
from left to right, the fluid enters the coil from the
center connection (Inlet) and exits from the bottom
(Outlet). The other coil connections should be
capped off (Cap).

A

3.75

2

1.5

B

Copper Sweat

0.75

1

Drain Connection

3

Outlet

Airflow

LFC-85

LFC-65

LFC-50

1.375

1.375

1.375

LFC-25

LFC-45

LFC-30

LFC-20

LCF-15

Unit Size

A

0.875

0.875

0.875

0.75

0.75

B (4 Row)

22.63

22.63

17.63

12.63

15.13

15.13

7.63

10.13

1.375

1.375

1.375

0.875

0.875

0.875

0.75

0.75

B (6 Row)

1.625

1.625

1.625

B (8 Row)

1.375
1.375
1.375
1.375
1.375

3.75

A

A

B

MSCF-20
MSCF-25
MSCF-30

Unit Size

MSCF-15

7.0

9.5

8.0

5.75

A

C (4 Row)

B (4 Row)

13.00
13.00

10.75

9.5

MSCF-45
MSCF-50
MSCF-65
MSCF-85

0.75

3

Outlet

1

Drain Connection

0.75

3

Outlet

1

Drain Connection

C (6 Row)

B (6 Row)

C (8 Row)

B (8 Row)

0.625
0.625
0.875
0.875
0.875
0.875
1.125
1.125

0.625
1.375

0.625

1.375
1.375
1.375
1.375
1.375

0.625
0.625
0.875
0.875
0.875
1.125
1.125
1.125

0.625
1.375

0.625

1.375
1.375
1.375
1.375
1.375

0.625
0.625
0.875
0.875
0.875
0.875
1.125
1.125

1.375
1.375
1.375
1.625
1.625
1.625

1.375
1.375

Chilled Water 4,6 or 8 Row

Direct Expansion (DX)-Single Circuit-4,6 or 8 Row

3.75

MSCF-30

Unit Size

12.00

A

D (4 Row)

C (4 Row)

17.00
17.00

13.50

12.00

MSCF-45
MSCF-50
MSCF-65
MSCF-85

D (6 Row)

C (6 Row)

D (8 Row)

C (8 Row)

0.625

0.875
0.875

0.625

0.875
0.875

0.625

0.875
0.875

0.875

1.125
1.125

0.625

1.125

Direct Expansion (DXI)-Dual Circuit with 50/50 Face

Interlaced Construction-4,6 or 8 Row

Airflow

Airflow

B

9.50

7.75

7.00

9.50

7.00

0.625

0.625

0.625

0.625

0.625

0.875

0.625

0.875

0.625

0.875

0.625

0.875

0.875
0.875

1.125
1.125

JOHNSONRI

03/13/2009

1/1

LFC COIL DIMS

B

Copper Sweat

C

Copper Sweat

C

Copper Sweat

D

Copper Sweat

2

1.5

2

1.5

Direct Expansion (DXI) • Dual Circuit with 50/50 Face Interlaced Construction • 4, 6 or 8 Row

Distributor hookup is done inside module through 2-inch access hole.

Right side connection shown.