GarrettCom MAGNUM 6KM User Manual

Page 44

Advertising
background image

Magnum 6KM Mobile Ethernet Switch Installation and User Guide

07/10


39

www GarrettCom com

.

.

C2.0

MAGNUM 6KM, with DC Dual-Source option

The 6KM Switch models with the internal -48VDC, 12VDC, 24VDC,

110VDC, 125VDC and 250VDC Dual-Source power supply are designed for
installations where a battery plant is the power source, and where two separate power
sources are utilized in order to increase operational uptime and to simplify maintenance.

C3.0 DUAL-SOURCE

OPTION, THEORY OF OPERATION

The Dual-Source DC power option is designed using diodes inside of the

chassis on each DC power input line. A diode is placed in each of the four input lines
(behind the four external power
connection terminals) so that
power from an external source can
only flow into the unit. This
allows the unit to operate
whenever DC power is correctly
applied to either or both of the two

inputs.


C4.0

FEATURES AND BENEFITS OF THE DUAL-SOURCE DESIGN

a)

The Switch unit can receive power from either input, “A” or “B”. The hub will

normally draw its power from the DC source with the highest voltage at a given

time.
b) The Switch unit will not allow power to flow from a higher voltage input to a lower

voltage input, i.e. the two DC power sources are not mixed together by the hub.

c)

When one correct DC input is present, the Switch will receive power if the other DC

input is absent, or even if it is connected with reverse polarity or shorted or

grounded.
d) Reverse polarity connections, if they should accidentally occur on either input, will

not damage the Switch or power supply internally (nor will it blow the fuse in the

internal power supply) because of the blocking action of the diodes. This is true

even if one input connection is reversed while the Switch is operating from the other

source.
e)

The Switch will not receive power (and will not work) when both inputs are

simultaneously absent or are both incorrectly connected.


C5.0

6KM DUAL SOURCE INSTALLATION

This section describes the proper connection of the 12, 24, –48, 110, 125 and

250VDC dual source leads to the power input connector on the Magnum 6KM Switch.

The DC input connector on the Magnum 6KM Mobile Ethernet Switch is

located on the left front of the unit. The power terminals are connected as shown below,
and they are electrically floating inside the unit so that either may be grounded by the
user if desired. The chassis is “earth” or ground (GND).

The mating power cable connection to the 6KM switch is made utilizing a

RD24, locking, female connector. Simply align the keyed female connector to the 6KM
male connector and twist the threaded lock to secure.

Advertising