Section 1.3

OPERATIONAL ANALYSIS

GENERAL

Figure 1, below, is a block diagram of the Impact Plus
computer controlled RV generator. The diagram is
Intended only for the purpose of illustrating generator
operation. Refer to the actual wiring diagram for
wiring interconnections.

OPERATIONAL DESCRIPTION

1. The Impact Plus is a computer controlled generator that uses

an inverter to create a superior sine wave and maintain a
steady frequency of 60 Hz. The PERMANENT MAGNET
ROTOR is directly coupled to the ENGINE and rotates at the
same speed as the engine.

2. As the ROTOR turns, its magnetic field cuts across a number

of STATOR windings, to induce a voltage into those windings.
A voltage is induced into the following STATOR windings:

a. Phase 1 and 2 of the STATOR POWER WIND-

INGS (output leads AC1-AC2 and SL1-SL2).

b. The STATOR POWER SUPPLY WINDING with

output leads PS1-PS2.

c. The STATOR TIMING WINDING (output leads

TIM1-TIM2).

d. STATOR BATTERY CHARGE WINDING with

output leads 55, 66 and 77.

3. STATOR BATTERY CHARGE WINDING output is delivered to

the unit battery via a BATTERY CHARGE RECTIFIER (BCR)
and a 1 OHM, 50 WATT RESISTOR. The circuit is completed
through the battery to frame ground and back to the BATTERY
CHARGE WINDING via Wire 55.

4. Stator timing winding output is delivered to the A6060 circuit

board. The timing winding output is used to determine engine rpm.

5. The stator power supply winding output is delivered to the

inverter. This is the power supply for operation of the inverter.

6. Stator power winding output (phase 1 and 2) is delivered to two

separate bridge rectifiers, where it is rectified to DC. This
becomes the DC link voltage and is delivered to the inverter.

Page 1.3-1