Troubleshooting cont – Global Machinery Company G25 User Manual

Page 19

Advertising
background image

19

Troubleshooting cont.

DC circuit breaker

continually tripping

1. Overload

1. Reduce load

2. Faulty cords or equipment

2. Check for damaged, bare, or frayed wires on equipment. Replace.

3. Incorrect cables used

3. Check to make sure you are using the DC cables supplied with

the actual generator. Using the incorrect cables could result in

the crossing over of polarity. Only use the supplied DC cables

with the actual generator.

4. Mixed polarity

4. Check to make sure that the DC cables are connected to the

correct battery polarity terminals. That is positive (+) to positive

(+) and negative (-) to negative (-)

Generator

overheating

1. Generator overloaded

1. Reduce load

2. Insufficient ventilation

2. Move to adequate supply of fresh air

Generator stops

1. Generator may

have fallen over

1. Check to make sure that the generator is in it’s correct upright

position. If not take corrective action to put it in the upright position

2. Generator may

have ran out of oil

2. Check to make sure that the generator has oil in it. If not take

corrective action to top up the oil tank

3. Generator may have ran

out of Fuel

3. Check to make sure that the generator has fuel in it. If not take

corrective action to top up the fuel tank

4. Generator may not

be correctly ventilated

with free flowing air

4. Check and make sure that the generator is located in a

appropriately ventilated environment. If not relocate the

generator to a well ventilated location.

5. Generator fuel cap

breather set on the

closed position

5. Check that the generator fuel cap has the breather located

switch located on the “on” position, allowing air to mix with the

fuel. If the breather cap is located in the “off” position rotate

switch on the cap to the “on” position.

6. Generator air filter

may need cleaning

6. Remove the air filter. Check to make sure that the air filter is

clean. If required clean, dry and re-install the air filter.

7. Generator fuel filter

may be blocked

7. The internal in-line filter may be blocked. Contact your service

agent for a service/replacement of the fuel filter.