Operating data – Generac Power Systems Whisper - Test UL 2200 User Manual

Page 3

Advertising
background image

COMMERCIAL 70 kW

KW RATING

70

ENGINE SIZE

6.8 Liter V-10

GENERATOR OUTPUT VOLTAGE/KW - 60 Hz

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

70 LP / 68 NG

291.6 LP / 283.3 NG

300

120/208V, 3-phase, 0.8 pf

70 LP / 68 NG

243.1 LP / 236.2 NG

300

120/240V, 3-phase, 0.8 pf

70 LP / 68 NG

210.7 LP / 204.7 NG

250

277/480V, 3-phase, 0.8 pf

70 LP / 68 NG

105.3 LP / 102.4 NG

125

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase

145

480V

3-phase

160

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft3/hr.) (gal/hr.)

cu

ft/hr

Exercise

cycle

110

1.20

44.2

25% of rated load

260

2.85

104.9

50% of rated load

499

5.46

200.9

75% of rated load

696

7.62

280.4

100% of rated load

1020

11.17

411


ENGINE COOLING
Air

flow

(inlet air including alternator and combustion air)

ft3/min. 5200

System coolant capacity

US gal.

4.5

Heat rejection to coolant

BTU/hr.

287,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

205


SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode

61

db(A) @ 23 feet at normal operating load

65


EXHAUST
Exhaust flow at rated output 60 Hz

cfm 557

Exhaust temp. at muffler outlet

°F

890

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

1800

HP at rated KW

60 Hz

110.7

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature

Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude

Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

COMMERCIAL 70 kW

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power
and condition, etc.

COMMERCIAL SERIES