3 manual transfer and start-up, 4 engine governor adjustments, 6 system ready led – Generac Power Systems 005040-2 User Manual

Page 16

Advertising
background image

14 Generac

®

Power Systems, Inc.

3.2.6 SYSTEM READY LED

The System Ready LED (green) has two main pro-
poses. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.

The system ready LED will be OFF when the switch
is in the manual or OFF positions.

The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.

This secondary function is only available with dip
switch two in the OFF position (ATS - automatic
transfer switch application).

3.3

MANUAL TRANSFER AND
START-UP

To transfer electrical loads to the Standby (EMER-
GENCY) power source side and start the engine man-
ually, refer to the Owner’s Manual of the particular
transfer switch.

3.4

ENGINE GOVERNOR
ADJUSTMENTS

Engine speed governing is also controlled by the
engine control board. The engine governor has been
set by the factory during final testing of the generator
and should not be adjusted.

If, however, adjustments are necessary, the following
procedure should be followed (Figure 3.2 and Section
3.8):

1. Move dip switch 8 to the test mode (OFF posi-

tion).

2. Set all three potentiometers (pots) fully counter-

clockwise.

‹

Section 3 - Operation

Guardian Liquid-cooled 25 kW Generator

Condition

System

Low

Low

High

Over

Over

Switch Position

Ready (Green)

Bat (Red)

Oil (Red)

Temp (Red)

Speed (Red)

Crank (Red)

Manual

Auto

Off

Generator Switch is

OFF

X

OFF

OFF

OFF

OFF

O

in the OFF Mode.

System Ready for

ON

X

OFF

OFF

OFF

OFF

O

Automatic Start

Generator Switch is

OFF

X

OFF

OFF

OFF

OFF

O

in the MANUAL Mode

Weekly Exerciser

X

Flashing

Flashing

Flashing

Flashing

Flashing

O

O

O

is not set

(-----------------------------------1 sec rate---------------------------------------)

Battery Voltage <12V

X

ON

O

O

O

for >1 minute

(Non-latching)

Battery Voltage <6V

X

ON

O

O

Unit Shutdown due

OFF

X

ON

O

O

to Low Oil Pressure

Unit Shutdown due

OFF

X

ON

O

O

to High Temperature

Unit Shutdown due

OFF

X

ON

O

O

to Engine Overspeed

Unit Failed to Start

OFF

X

ON

O

O

during it’s Crank Cycle

Utility Voltage is

Flashing

X

O

O

<45% of Nominal

1 sec rate

Engine Speed Signal Fault

OFF

X

Flashing

O

O

Control Board is

OFF

X

The five RED LED’s will turn on one at a time

O

O

O

in GTS Mode

X = indicates that the LED can be ON or OFF depending on the operating conditions.

Advertising