2 cord sets and connection plugs, 3 how to use the generator – Generac GP 3250 Portable Generator 005982-0 User Manual

Page 8

Advertising
background image

6

2.2 CORD SETS AND CONNECTION PLUGS

2.2.1 120 VAC DUPLEX RECEPTACLE

This is a 120 Volt outlet protected against overload by a 14 Amp circuit
breaker (Figure 7). 14 Amps of current may be drawn from each socket,
however, total power drawn must be kept within data plate ratings. Use
only high quality, well insulated, 3-wire grounded cord sets rated for 125
Volts at 20 Amps (or greater).

2.2.2 120/240 VAC, 20A TWISTLOCK RECEPTACLE

This is a 120/240 Volt outlet protected against overload by a 14
Amp circuit breaker (Figure 7). Connect a suitable 4-wire grounded
cord set to the plug and to the desired load. The cord set should
be rated for 250 volts at 20 amps (or greater) if the 120/240
receptacle is used along with 120 volt receptacle. The total load
drawn must not exceed the data label ratings.
IMPORTANT: Do not overload the generator. Also, do not overload
individual panel receptacles. These outlets are protected against
overload with circuit breakers. If amperage rating of any circuit
breaker is exceeded, that breaker opens and electrical output
to that receptacle is lost. Read “Don’t Overload the Generator”
carefully.

Figure 7 - 120 VAC Duplex & 120/240 VAC Twistlock

2.3 HOW TO USE THE GENERATOR

If there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.

n

Never operate in an enclosed area or
indoors! NEVER use in the home, or in

partly enclosed areas such as garages,

even if doors and windows are open! ONLY

use outdoors and far from open windows,

doors, vents, and in an area that will not

accumulate deadly exhaust.

n

The engine exhaust fumes contain carbon

monoxide, which can you cannot see or

smell. This poisonous gas, if breathed

in sufficient concentrations, can cause

unconsciousness or even death.

n

Adequate, unobstructed flow of cooling and

ventilating air is critical to correct generator

operation. Do not alter the installation or

permit even partial blockage of ventilation

provisions, as this can seriously affect safe

operation of the generator. The generator

MUST be operated outdoors.

n

This exhaust system must be properly

maintained. Do nothing that might render the

exhaust system unsafe or in noncompliance

with any local codes and/or standards.

n

Always use a battery operated carbon

monoxide alarm indoors, installed according

to the manufacturers instructions.

2.3.1 GROUNDING THE GENERATOR

The National Electrical Code requires that the frame and
external electrically conductive parts of this generator be
properly connected to an approved earth ground (Figure 8)
.
Local electrical codes may also require proper grounding of the
unit. For that purpose, connecting a No. 10 AWG (American Wire
Gauge) stranded copper wire to the grounding lug and to an
earth-driven copper or brass grounding rod (electrode) provides
adequate protection against electrical shock. However, local codes
may vary widely. Consult with a local electrician for grounding
requirements in the area.
Proper grounding of the generator will help prevent electrical
shock
in the event of a ground fault condition in the generator
or in connected electrical devices. Proper grounding also helps
dissipate static electricity, which often builds up in ungrounded
devices.

Figure 8 - Grounding the Generator

Operation

Advertising