COMMERCIAL 45 kW CA

KW RATING

45

ENGINE SIZE

2.4 Liter

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/208V, 3-phase, 0.8 pf

45

156.3

175

120/240V, 3-phase, 0.8 pf

45

135.4

150

277/480V, 3-phase, 0.8 pf

45

67.7

80

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
208

3-phase

100

480V

3-phase

110

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft

3

/hr.) (gal/hr.)

cu

ft/hr

Exercise

cycle

102

1.11

40.4

25% of rated load

194

2.12

77.1

50% of rated load

373

4.07

148

75% of rated load

520

5.67

206.3

100% of rated load

720

7.86

286


ENGINE COOLING
Air

flow

(inlet air including alternator and combustion air)

ft

3

/min. 2,725

System coolant capacity

US gal.

3.0

Heat rejection to coolant

BTU/hr.

173,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

144


SOUND EMISSIONS IN DBA
Exercising at 7 meters

58

Full load at 7 meters

72


EXHAUST
Exhaust flow at rated output 60 Hz

cfm 429

Exhaust temp. at muffler outlet

°F

1150

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

3600

HP at rated KW

60 Hz

71

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature

Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude

Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

COMMERCIAL 45 kW CA

RATING: All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to
varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change
without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.

COMMERCIAL SERIES