SERIES 41 AND 81 MODUTROL IV™ MOTORS

7

63-2187—3

Fig. 6. Typical connections for Series 41 Motors.

Fig. 7. Typical connections for Series 81 Motors.

Fig. 8. Power connections for Series 41 Line Voltage

Motors controlling two-position outside air dampers.

Fig. 9. Power connections for Low Voltage Motors

controlling two-position outside air dampers.

Fig. 10. Wiring connections for Series 81 Motors

controlling two-position pre-heat coil valves.

SETTINGS AND ADJUSTMENTS

Stroke Setting

On adjustable stroke motors, the stroke is field adjustable and

can be set between 90° and 160°. A mechanical adjustment

(cam) establishes the fully open (clockwise, viewed from the

power end) and fully closed positions of the motor shaft

(see Fig. 2). TRADELINE motors are factory set for 160°.

IMPORTANT

— Detach linkage from motor before adjusting stroke.

— Instructions are for normally closed models. Reverse

for normally open.

Before Setting Stroke

1. Remove top cover from motor.

2. Disconnect controller from motor.

MOTOR

1

1

M806A

THERMOSTAT

LIMIT CONTROL

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

MOTOR

1

M807A

THERMOSTAT

LIMIT CONTROL

TRANSFORMER

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

MOTOR

1

M808A

MOTOR

STARTER

BLOWER

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

24V

MOTOR

1

M809A

TRANSFORMER

MOTOR

STARTER

BLOWER

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

1

24V

MOTOR

1

M809A

TRANSFORMER

MOTOR

STARTER

BLOWER

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.