6

15

ON and Alarm Silencer Switch

16

OFF Switch

17

Previous Page or Setting Change

18

Next Page

19

Special Function Log in /out

20

Enter or Reconfirmed

21

Utility Input Normal LED

22

Bypass Input Normal LED

23

UPS under Redundancy Mode

24

UPS under ECO Mode

25

UPS Fault or Abnormal Warning LED

26

EPO

Emergency Power Off

27

Er01

DC BUS capacitor pre-charge abnormal after
50-seconds or Battery Fuse failure

28

Er02

AC SCR or Battery SCR soft Start abnormal
after 2-seconds

29

Er03

PFC (Boost) soft start abnormal after 30-
seconds

30

Er04

Inverter Failure

31

Er05

Battery Weak or Dead

7

32

Er06

Output Short Circuit

33

Er08

DC Bus high-voltage-level abnormal

34

Er09

DC Bus low-voltage-level abnormal

35

Er10

Inverter Over-current

36

Er11

UPS Overheated

37

Er12

Inverter Overload

38

Er13

Charger Failure or Abnormal

39

Er14

Fan Failure

40

Er15

Wrong procedure to enter Maintenance Mode

41

Er16

Output parameters Set error in Parallel System

42

Er17

ID numbers are in conflict in Parallel System or
ID number error in single unit

43

Er18

EEPROM data error. Its values are reset to
default (Normal / 220V / adj0% / +/-3Hz / low
sensitivity)

44

Er20

DC Bus voltage cannot be discharged

45

Er21

Parallel communication error (communication
wire disconnected or failure to find ID1 UPS) in
parallel system

46

Er22

Bypass SCR or Output Fuse Fails

47

Er23

Inverter Relay or SCR or Output Fuse Fails