PARAMETERS

21

Func-

tion

Parameter

Number

Name

Setting Range

Minimum

Setting

Increments

Factory Setting

Refer To

Page:

<Note9>

150

Output current detection level

0 to 200%

0.1%

150%

120

151

Output current detection period

0 to 10 sec

0.1 sec

0

120

152

Zero current detection level

0 to 200%

0.1%

5.0%

121

C

urrent

det

ec

tion

153

Zero current detection period

0 to 1 sec

0.01 sec

0.5 sec

121

154

Voltage reduction selection during stall
prevention operation

0, 1

1

1

121

155

RT activated condition

0, 10

1

0

122

*156

Stall prevention operation selection

0 to 31 (Odd), 100

1

0

122

157

OL signal waiting time

0 to 25 sec, 9999

0.1 sec

0

124

Sub f

unc

tions

158

AM terminal function selection

1 to 3, 5 to 14,

17, 18, 21

1

1

124

Addit

ional

fu

ncti

on

160

User group read selection

0, 1, 10, 11

1

0

125

162

Automatic restart after instantaneous
power failure selection

0, 1, 2

1

0

125

163

First cushion time for restart

0 to 20 sec

0.1 sec

0 sec

125

164

First cushion voltage for restart

0 to 100%

0.1%

0%

125

A

uto

ma

tic r

esta

rt

a

fte

r

ins

tant

aneous

pow

er

fa

ilure

*165

Restart stall prevention operation level

0 to 150%

0.1%

150%

125

170

Watt-hour meter clear

0



0

126

In

itial

m

onit

or

171

Actual operation hour meter clear

0



0

126

173

User group 1 registration

0 to 999

1

0

125

174

User group 1 deletion

0 to 999, 9999

1

0

125

175

User group 2 registration

0 to 999

1

0

125

U

ser f

unc

tions

176

User group 2 deletion

0 to 999, 9999

1

0

125

180

RL terminal function selection

0 to 99, 9999

1

0

126

181

RM terminal function selection

0 to 99, 9999

1

1

126

182

RH terminal function selection

0 to 99, 9999

1

2

126

183

RT terminal function selection

0 to 99, 9999

1

3

126

184

AU terminal function selection

0 to 99, 9999

1

4

126

*185

JOG terminal function selection

Already Assigned

126

186

CS terminal function selection

0 to 99, 9999

1

6

126

190

RUN terminal function selection

0 to 199, 9999

1

0

128

191

SU terminal function selection

0 to 199, 9999

1

1

128

192

IPF terminal function selection

0 to 199, 9999

1

2

128

193

OL terminal function selection

0 to 199, 9999

1

3

128

194

FU terminal function selection

0 to 199, 9999

1

4

128

T

erm

inal as

si

gnm

ent

f

unc

tions

195

A, B, C terminal function selection

0 to 199, 9999

1

99

128

Addit

ional

fu

ncti

on

199

User's initial value setting

0 to 999, 9999

1

0

130

Pr.185 : This terminal is already assigned in Factory. User can not use.

Advertising