MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 25

Advertising
background image


MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-6

2.) Battery log (FIGURE 2.10)

This screen displays the cumulative battery discharging record.

FIGURE 2.10 Battery log screen

2.4.2 INPUT POWER FAILURE

During an Input Power Failure, the UPS inverter will be powered by the UPS batteries.
The following will be displayed on the main and measurement screen (Indication of
battery remaining capacity).

FIGURE 2.11 Main screen FIGURE 2.12 Measurement screen

(Battery operation) (Battery operation)

The LCD will display a battery low voltage message when the battery capacity is near
depletion. The End of Battery Discharge announcement is displayed when the battery
end voltage is reached. At this time, the inverter will perform an electronic shutdown to
prevent battery loss of life typical from extreme deep discharge conditions. When the
input power is restored, the inverter will automatically restart to power the load, and
the batteries will be simultaneously recharged. The End of Battery announcement is
shown at the bottom of the screen.

480V

48A

52RC

52C

72B

STS

480V

48A
48A
48A

48A

32kW

36A