Specifications – MITSUBISHI ELECTRIC PRH-5 User Manual

Page 9

Advertising
background image

- 8 -

SPECIFICATIONS

ITEM

PR-5YC

PRH-5YA

PRH-5YA-L

PR-8YC

PRH-8YA

PRH-8YA-L

PR-10YC

PRH-10YA

PRH-10YA-L

PR-15YC

PRH-15YA

PRH-15YA-L

PR-20YC

PRH-20YA

PRH-20YA-L

16.3

23.8

29.7

46.3

60.8

TOTAL COOLING CAPACITY

BTU/h

55,600

81,300

101,200

157,900

207,500

(GROSS)

kcal/h

14,000

20,500

25,500

39,800

52,300

kW

kW

13

19.7

25.3

38.4

50.2

SENSIBLE COOLING CAPACITY

BTU/h

44,400

67,100

86,500

130,900

171,400

(GROSS)

kcal/h

11,200

16,900

21,800

33,000

43,200

kW

15.1

23

32

45.5

61.2

TOTAL

HEATING CAPACITY

BTU/h

51,600

78,600

109,100

155,100

208,700

(GROSS)
(PRH-YA,PRH-YA-L ONLY)

kcal/h

13,000

19,800

27,500

39,100

52,600

CAPACITY STEPS

%

0-100

0 - 5 0 - 1 0 0

REFRIGERANT

R22 (FACTORY CHARGED)

REFRIGERANT CONTROL

CAPILLARY TUBE

EXTERNAR FINISH

ACRYLIC RESIN COATING

COLOR (MUNSELL NO.)

MUNSELL 5Y8/1

HEIGHT

mm

1,000

1,200

DIMENSION

WIDTH

mm

1,000

1,300

1,990

DEPTH

mm

1,600

1,840

NET WEIGHT

kg

299

393

413

698

729

COMPRESSOR

HERMETIC LINE START (RECIPROCATING)

MOTOR OUTPUT

kW

3.73

5.6

7.5

2

X

X

X

X

X

X

X

X

X

X

5.6

2 7.5

INDOOR COIL

CROSS FIN COIL

FAN

CENTRIFUGAL (GALVANIZED STEEL) - BELT DRIVE

FAN MOTOR

THREE PHASE CAGE INDUCTION MOTOR

FAN MOTOR OUTPUT

kW

0.75

1.1

1.5

2.2

3

CMM

54

84

100

168

190

NOMINAL AIR FLOW

CFM

1,907

2,967

3,532

5,934

6,711

L/S

900

1,400

1,660

2,800

3,160

EXTERNAL STATIC

mmAq

10

10

10

20

20

PRESSURE

Pa

100

100

100

200

200

OUTDOOR COIL

CROSS FIN COIL

FAN

PROPELLER - DIRECT DRIVE

FAN MOTOR

THREE PHASE CAGE INDUCTION MOTOR

FAN MOTOR OUTPUT

kW

0.15

0.35

0.35

2 0.35

2 0.35

CMM

95

185

185

2 185

2 185

NOMINAL AIR FLOW

CFM

3,355

6,534

6,534

2 6,534

2 6,534

L/S

1,583

3,083

3,083

2 3,083

2 3,083

DRAIN CONNECTION

mm

25.4

HIGH PRESSURE SWITCH,FUSE

PROTECTION DEVICES

OVER CURRENT RELAY (COMP. & INDOOR FAN,OUTDOOR FAN )

INTERNAL THERMOSTAT (COMP. & OUTDOOR FAN )

ANTI SHORT-CYCLE TIMER, FREEZE & FROST PROTECTOR

NOTE

1. NOMINAL COOLING & HEATING CAPACITIES ARE BASED FOLLOWING CONDITIONS.

COOLING : INDOOR:27˚CDB, 19˚C WB ; OUTDOOR:35˚C DB.
HEATING : INDOOR:21˚C DB ; OUTDOOR:7 DB, 6˚C WB.

2. CAPACITIES ARE GROSS CAPACITIES WHICH DO NOT INCLUDE A DEDUCTION FOR EVAPORATOR

FAN MOTOR HEAT.

Advertising
This manual is related to the following products: