MDM45 Digital Loop Monitor SWICHGAGE

®

Instructions for Installation and Operation

B

®

MDM-9114N

Revised 06-97

Section 05

(00-02-0160)

Description

The MDM45 is a 4-1/2 in. (114 mm) dial digital loop monitor with low and
high trip points which are adjustable over the full range of the monitor. A tog-
gle switch and a push button are provided in the face of the monitor for easy
access to the trip point adjustments. The MDM45 accepts one 4-20 mA trans-
mitter input. It is designed to operate from 12 or 24 VDC systems.

Specifications

Accuracy: ±1.0% of full scale.
Operating Temperature Range: 32 to 155°F (0 to 70°C).
Storage Temperature: -40 to 300°F (-40 to 150°C).
Case Material: Aluminum.
Display Range: -10,000 to 19,999.
Signal Input: 4–20 mA.
Input Resistance: 250 Ohms.
Display Update Time: 0.5 seconds.
Power Input: 1.8 watts @ 12 VDC; 3.6 watts @ 24 VDC.
Trip Point Output: A power FET switch turns on when signal reaches the trip

point. Trip points can be selected to open or close, (0.5 A @ 250 VDC).

* Laboratory Approvals: MDM45 is CSA approved for Class I, Division 2,

Group D, hazardous areas. Digital loop monitor input 10–30 VDC, 4–20 mA.

NOTE: MDM45 is for use with Electromechanical TATTLETALE

®

annunci-

ators or SELECTRONIC

®

or similar solid-state annunciators.

About Trip Points

During normal operation, both trip points are always active and are indepen-
dent of the trip point selector switch. When the transmitter signal meets the
high or low trip point, that trip point is triggered: the trip point output “turns
on”, and an LED light to indicate the output is ON.

Open Transmitter Input

An open transmitter input causes the SWICHGAGE

®

to go negative, trigger-

ing the low trip point if the trip point is being used.

Warranty

A two year limited warranty on materials and workmanship is provided with this
Murphy product. Details are available on request and are packed with each unit.

Mounting

The MDM45 has a flush mount case for installation in a panel from 1/32 in.
(1 mm) to 1/8 in. (3 mm) thick. We recommend to install the MDM45 within a
weatherproof enclosure to protect it from rain, dust, etc.
A round mounting hole size 4-3/4 in. (121 mm) diameter is needed for the
mounting. Three (3) screw holes 1/4 in. (6 mm) are also needed to secure
the unit to the panel (See mounting diagram).
With a straight edge screwdriver remove the three (3) screws located in the
front of the unit and install the unit from the back of the panel; secure firmly
in place by tightening the screws.

NOTE: A minimum distance of 12 in. (305 mm) from any ignition coil or
coil leads should be maintained.

Mounting Dimensions

Please read the following information before installing

.

A visual inspection for any damage which may

have occurred during shipping is recommended. It is your responsibility to have a qualified person install the
unit, and make sure it conforms with NEC and local codes.

GENERAL INFORMATION

Installation Accessories

●

Straight edge screw driver (medium).

●

Wire cutters, wire stripping and terminal crimping tool.

●

Potentiometer trimmer or small screwdriver with plastic handle.

●

4–20 mA simulator.

●

DC power supply (10–30 VDC, 150 mA minimum).

Made in USA

®

FRANK W.

MFR.

MDM45

DISPLAY

PUSH TO READ

TRIP POINT

LOW

TRIP PT

HIGH

TRIP PT

®

Approved

*

for

Class I, Division 2,
Group D Hazardous

Locations

WARNING: Disable the engine (motor) so it can NOT start.
Remove the battery ground cable (when applicable).

1/4 in.

(6 mm)

dia.

3 holes

120

120

120

2-39/64 in.

(66 mm)

radius

Mounting Hole

4-3/4 in. (121 mm)

diameter

panel

side view

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

✔

Disconnect all electrical power to the machine.

✔

Make sure the machine cannot operate during installation.

✔

Follow all safety warnings of the machine manufacturer.

✔

Read and follow all installation instructions.

Advertising