4 output terminal function parameters, 1 up-to-frequency (pr. 41 ), Output terminal function parameters – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 100

Advertising
background image

90

Output terminal function parameters

2.3.19

Start-time earth (ground) fault detection selection (Pr. 40

)

2.4 Output terminal function parameters

2.4.1

Up-to-frequency (Pr. 41

)

Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used for
SU signal output.

You can choose whether to make earth (ground) fault detection at start valid or invalid.
Earth (Ground) fault detection is executed only right after the start signal is input to
the inverter.
Protective function will not activate if an earth fault occurs during operation.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

40

Start-time earth
(ground) fault
detection selection

0

0, 1

0: Earth (Ground) fault

detection for protection is
not executed.

1: Earth (Ground) fault

detection for protection is
executed.

Setting is
enabled when
Pr. 30 = "1".

CAUTION

1. If an earth (ground) fault is detected with "1" set in Pr. 40, alarm output "

"

is detected and the output is shut off.

2. If the motor capacity is less than 0.1kW, earth (ground) fault protection may

not be provided.

REMARKS

When an earth (ground) fault is detected with "1" set in Pr. 40, an approximate 20ms delay
occurs at every start.

The ON range of the up-to-
frequency signal (SU) output
when the output frequency
reaches the running frequency
can be adjusted between 0 and
±100% of the running frequency.
This parameter can be used to
ensure that the running
frequency has been reached to
provide the operation start
signal etc. for related
equipment.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

41

Up-to-frequency

10%

0 to 100%

Setting is enabled when Pr. 30 = "1".

CAUTION

Using Pr. 64 or Pr. 65 to change the terminal assignment may affect the other functions.
Please make setting after confirming the function of each terminal. (Refer to page 104.
)

Related parameters

Assignment of SU signal to terminal

Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C

terminal function selection" (refer to page 104)

Running
frequency

Adjustable
range

Output signal
(SU)

Time

Start signal

O

u

tput

fr

eq

uenc

y (

H

z)

Pr.41

OFF

ON

OFF

ON

OFF

Advertising
This manual is related to the following products: