10 operation selection function parameters – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 115

Advertising
background image

105

Operation selection function parameters

2

F

UNCT

IO

NS

2.10 Operation selection function parameters

2.10.1 Retry function (Pr. 66

, Pr. 67

, Pr. 68

, Pr. 69

)

<Setting>

•Use Pr. 66 to select the protective functions (major faults) to be activated for retries.

*

Indicates the retry items selected. (OCT denotes any of OC1 to OC3 and OVT

any of OV1 to OV3.)

•Use Pr. 67 to set the number of retries at alarm occurrence.

* If the retry count is exceeded, "

" (retry count over) is displayed.

•Use Pr. 68 to set the waiting time from when an inverter alarm occurs until a restart in

the range 0.1 to 360s.

•Reading the Pr. 69 value provides the cumulative number of successful restart times

made by retry. The cumulative number of time is cleared when setting value "0" is
written.

When any protective function (major fault) is activated and the inverter stops its
output, the inverter itself resets automatically and performs retries. Whether
retry is performed or not, alarms reset for retry, number of retries made and
waiting time can be selected.
When you have selected automatic restart after instantaneous power failure
(with speed search), restart operation is performed at the retry operation time
which is the same of that of a power failure. (Refer to page 96 for automatic
restart function.)

Parameter

Name

Factory

Setting

Setting

Range

Remarks

66

Retry selection

0

0 to 3

Setting is enabled when
Pr. 30 = "1"

67

Number of retries at alarm
occurrence

0

0, 1 to 10,

101 to 110

68

Retry waiting time

1s

0.1 to 360s

69

Retry count display erase

0

0

Pr. 66

Setting

Protective Functions (Major Faults) for Retries

OCT OVT THM THT

BE

FIN

GF

OHT OLT

PE

PUE RET CPU OPT

0

1

2

3

Pr. 67 Setting

Number of Retries

Alarm Signal Output

0

Retry is not made.



1 to 10

1 to 10 times

Not output every time *

101 to 110

1 to 10 times

Output every time

Advertising