3 voltage input selection (pr. 73 ) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 118

Advertising
background image

108

Operation selection function parameters

2.10.3 Voltage input selection (Pr. 73

)

You can change the input (terminal 2) specifications according to the frequency
setting voltage signal. When entering 0 to 10VDC, always make this setting.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

73

0-5V/0-10V
selection

0

0, 1

Terminal 2 input voltage
0: 0-5VDC input
1: 0-10VDC input

Setting is enabled
when Pr. 30 = "1"

CAUTION

The acceleration/deceleration time, which is a slope up/down to the

acceleration/deceleration reference frequency, is not affected by the change
in Pr. 73 setting.

When connecting a frequency setting potentiometer across terminals 10-2-5

for operation, always set "0" in this parameter.