4 input filter time constant (pr. 74 ), 5 reset selection/pu stop selection (pr. 75 ) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 119

Advertising
background image

109

Operation selection function parameters

2

F

UNCT

IO

NS

2.10.4 Input filter time constant (Pr. 74

)

<Setting>

Increase the filter time constant if steady operation cannot be performed due to noise.
A larger setting results in slower response. (The time constant can be set between
approximately 1ms to 1s with the setting of 0 to 8. A larger setting results in a larger
filter time constant.)

2.10.5 Reset selection/PU stop selection (Pr. 75

)

<Setting>

You can set the input section's built-in filter constant for an external voltage or
current frequency setting signal.

Effective for eliminating noise in the frequency setting circuit.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

74

Input filter time
constant

1

0 to 8

Setting is enabled when Pr. 30 = "1"

You can make reset input acceptance selection and choose the stop function
from the operation panel (PU).

Reset selection

:You can choose the reset function input (RES signal) timing.

PU stop selection :When an alarm etc. occurs in any operation mode, you can

make a stop from the operation panel by pressing the

.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

75

Reset selection/
PU stop selection

14

0, 1, 14, 15 Setting is enabled when Pr. 30 = "1"

Pr. 75

Setting

Reset Selection

PU Stop Selection

0

Reset input normally enabled.

The PU stop key is invalid. Note that the

is

valid only in the PU operation mode or combined
operation mode (Pr. 79 = "4").

1

Enabled only when the protective
function is activated.

14

Reset input normally enabled.

Pressing the

decelerates the inverter to a

stop in any of the PU, external and communication
operation modes.

15

Enabled only when the protective
function is activated.

STOP

RESET

STOP

RESET

STOP

RESET