1 standard connection diagram – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 12

Advertising
background image

2

Standard connection diagram and terminal specifications

1.1 Standard connection diagram and terminal

specifications

1.1.1

Standard connection diagram

Three-phase 200V power input
Three-phase 400V power input

REMARKS

*1.

The N/- terminal is not provided for the FR-S520E-0.1K to 0.75K.

*2.

The PR terminal is provided for the FR-S520E-0.4K to 3.7K.

*3.

Not needed when the setting dial is used for calibration.
Used when calibration must be made near the frequency meter for such a reason as a remote frequency meter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected.
In this case, use this resistor and setting dial together.

*4.

You can switch the position of sink and source logic. Refer to page 26.

*5.

When the setting potentiometer is used frequently, use a 2W1k

potentiometer.

*6.

The terminal functions change with input terminal function selection (Pr. 60 to Pr. 63). (Refer to page 102.)
(RES, RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, X14, X16, (STR) signal selection)

*7.

The terminal function changes according to the setting of output terminal function selection (Pr. 64, Pr. 65).
(Refer to page 104.) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, Y93, Y95, LF, ABC signal selection)

Inverter

Motor

IM

U

V

W

RUN

SE

Running

Alarm output

Operation status
output

Open

collector

Open collector
outputs

A

B

C

Frequency setting
potentiometer

1/2W1k

Frequency setting signals (Analog)

10

2

2

3

1

4 to 20mADC(+)

4

0 to 5VDC
0 to 10VDC

5

Current input(-)

(+5V)

(Common)

(4 to 20mADC)

Selected

output
common

Low speed

RL

NFB MC

Power factor improving
DC reactor
(FR-BEL: Option)

Jumper: Remove this
jumper when FR-BEL
is connected.

P1

SINK

SOURCE

Multi-speed

selection

Take care not to short
terminals PC-SD.

RS-485

Connector

Three-phase AC
power supply

Control circuit terminal

Main circuit terminal

When using the current input as
the frequency setting signal, set
"4" in any of Pr. 60 to Pr. 63 (input
terminal function selection), assign
AU (current input selection) to any
of terminals RH, RM, RL and STR
and turn on the AU signal.

Control input
signals
(No voltage
input allowed)

STF

STR

RM

Forward rotation start
Reverse rotation start

Middle speed

High speed

RH

*3

FM

SD

(+)

Calibration
resistor

(-)

Earth (Ground)

R

Brake resister

Earth
(Ground)

External transistor common
24VDC power supply
Contact input common (source)

SD

PC

Contact input common

Indicator
1mA full-scale
Analog meter
(Digital indicator)

*6

*4

*6
*6
*6

*7

*7

*7

*7

*1

*2

*5

PR

R/L1

S/L2

T/L3

P/+

N/-

Advertising
This manual is related to the following products: