Operation selection function parameters

2

F

UNCT

IO

NS

2.10.6 Cooling fan operation selection (Pr. 76

)

<Setting>

CAUTION

Do not reset the inverter with the start signal on.
Otherwise, the motor will start instantly after resetting, leading to
potentially hazardous conditions.

You can control the operation of the cooling fan built in the inverter (whether
there is a cooling fan or not depends on the model.).

Parameter

Name

Factory

Setting

Setting

Range

Remarks

76

Cooling fan
operation
selection

0

0, 1

0: Operation is performed with

power on.

1: Cooling fan ON/OFF control

Setting is
enabled when
Pr. 30 = "1"

Setting

Description

0

Operated at power on (independent of whether the inverter is running or at a stop).

1

Cooling fan ON/OFF control valid

Always on during inverter operation
During stop (reset or error), the inverter status is monitored and the fan is

switched on/off according to the temperature.

Heatsink temperature is less than 40

o

C ..........................Cooling fan off

Heatsink temperature is not less than 40

o

C ....................Cooling fan on

REMARKS

In either of the following cases, fan operation is regarded as faulty,

is shown on the

operation panel, and the minor fault (LF) signal is output. Use any of Pr. 64, Pr. 65 (output
terminal function selection) to allocate the terminal used to output the LF signal.*
•Pr. 76 = "0"

When the fan comes to a stop with power on.

•Pr. 76 = "1"

When the inverter is running and the fan stops during fan ON command.

CAUTION

* When the terminal assignment is changed using Pr. 64, Pr. 65, the other

functions may be affected. Confirm the functions of the corresponding
terminals before making settings.