8 reverse rotation prevention selection (pr. 78 ), 9 operation mode selection (pr. 79 ), E 113 – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 123: Age 113)

Advertising
background image

113

Operation selection function parameters

2

F

UNCT

IO

NS

2.10.8 Reverse rotation prevention selection (Pr. 78

)

<Setting>

2.10.9 Operation mode selection (Pr. 79

)

This function can prevent reverse rotation faults resulting from the incorrect

input of the start signal.

POINT

Used for a machine which runs only in one direction, e.g. fan, pump.

(The setting of this function is valid for the combined, PU, external and

communication operations.)

Parameter

Name

Factory

Setting

Setting

Range

Remarks

78

Reverse rotation
prevention selection

0

0, 1, 2

Setting is enabled when Pr. 30 = "1"

Pr. 78 Setting

Function

0

Both forward and reverse rotations allowed

1

Reverse rotation disallowed

2

Forward rotation disallowed

Used to select the operation mode of the inverter.

The inverter can be run from the operation panel or parameter unit (PU
operation), with external signals (external operation), or by combination of PU
operation and external operation (external/PU combined operation).
The inverter is placed in the external operation mode at power on (factory
setting).

Parameter

Name

Factory Setting

Setting Range

79

Operation mode selection

0

0 to 4, 7, 8